UPS SYSTEM INSTALLATION
4.8.2Battery Power Wiring
C A U T I O N
When sizing the battery system, do not exceed the internal battery charger capabilities. See Chapter 10,
To install wiring to connections:
NOTE An installed FI−UPM is always designated as UPM 4.
1.Route the battery cables between the ISBM section and the battery system or battery disconnect. See Figure
2.If wiring the UPS for a common battery, proceed to Step 3; if wiring for a separate battery, proceed to Step 5.
3.Using hardware from the external wiring terminal hardware kit (see Table
Use both sets of terminals shown in Figure
4.Proceed to Step 6.
5.Using hardware from the external wiring terminal hardware kit (see Table
6.After wiring the UPS system to the facility power and critical load, be sure to ground the system according to local and/or national electrical wiring codes.
7.If wiring interface connections, proceed to paragraph 4.9; otherwise, proceed to Step 8.
8.When all wiring is complete, reinstall the top and bottom safety shield panels removed in paragraph 4.8.1, Step 2 on page 4−18. Secure with the retained hardware.
9.Reinstall the left front panel removed in paragraph 4.8.1, Step 1 on page 4−18 and secure with the retained hardware.