UPS OPERATING INSTRUCTIONS

Table 7-3.Display Menu Operation (continued)

Function

Subfunction

Operation

 

 

 

 

Com Port Selection

The Com Port Setup screen allows selection of the serial COM port to set up. Select COM PORT

 

 

SETUP from the System Setup Level 1 menu to display the COM Port Setup screen. Use the up or

 

 

down arrow pushbutton to highlight the the COM port to be set up, then press the SELECT

 

 

pushbutton. To return to the System Setup screen, press the return arrow pushbutton.

 

 

 

 

Com Port Setup

The COM Setup screen is used to change and save the settings for the selected serial

 

 

communication port. The COM port number selected from the COM Port Setup screen displays.

 

 

If the changes are not wanted, use the ABORT pushbutton to return to the COM Port Setup

 

 

screen. Use the up or down arrow pushbutton to highlight the setting to be changed. Use the

 

 

return arrow pushbutton to toggle through the values for the setting to make the change. Press

 

 

SAVE or ABORT. Once the action is completed, the COM Port Setup screen is displayed.

 

 

 

Control

 

See paragraph 7.2.7 for details.

 

 

 

7.2.7System Status Screen and Controls

Press the CONTROLS pushbutton on the main menu bar to display the System Status screen. Normal operation, transfer to bypass, charger control, UPM startup and shutdown and LOAD OFF commands are controlled through this screen. In addition, the screen displays the current status of the UPS and indicates whether the UPS is in Maintenance Bypass or Bypass, and the state of the UPM and battery charger. Figure 7-5shows the System Status screen.

Use the or pushbutton on the System Status menu bar to highlight the command screen desired, then press the CONTROLS pushbutton to display the command menu screen.

Table 7-4lists the typical System Status Screen Messages that are displayed during

UPS operation.

Table 7-5describes the control functions and provides instructions to access and use the command menu screens.

For detailed information about using the System Controls, see paragraph 7.3.

 

 

 

 

 

 

 

 

 

 

SYSTEM

STATUS

 

 

 

 

 

UPS

:

SHUTDOWN

 

 

 

 

 

BYPASS

:

AVAILABLE

 

 

 

 

 

MAINTENANCE BYPASS

: OFF

 

 

 

 

 

CHARGER

: OFF

 

 

 

 

 

UPM: OFFLINE

 

 

 

 

 

 

 

 

CONTROLS

ESC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 7-5. Typical System Status Screen

7−8

EATON Powerware® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com

Page 150
Image 150
Powerware 650825 kVA operation manual System Status Screen and Controls, Function Subfunction Operation Com Port Selection