UPS INSTALLATION PLAN AND UNPACKING

For external wiring requirements, including the minimum AWG size of external wiring, see Table 3-4for installations using a common battery system, Table 3-5for installations using a separate battery system, or Table 3-6for separate rectifier feed installations. Wire sizes listed are for copper wiring only.

Table 3-4. Input/Output Ratings and External Wiring Requirements for the Powerware 9395−825/650, 9395−825/750, and 9395−825/825

– Common Battery

 

Units

 

 

 

Rating 50/60 Hz

 

 

Basic Unit Rating

 

 

 

 

 

 

 

kVA

650

650

750

750

825

825

 

kW

585

591

675

682

7742

750

 

 

 

 

 

 

 

 

Input and Output Voltage

Volts

400/400

480/480

400/400

480/480

400/400

480/480

 

 

 

 

 

 

 

 

AC Input to UPS Rectifier (0.98 Minimum pF)

 

 

 

 

 

 

 

Full load current plus battery recharge current

(3) Phases, (1) Ground

Amps

1079

891

1245

1028

1369

1130

A

Minimum Conductor Size

 

AWG or kcmil

500

500

500

500

500

500

Number per Phase

 

(each)

(4)

(3)

(4)

(4)

(5)

(4)

 

 

 

 

 

 

 

 

 

AC Input to UPS Bypass (Four Wire)

 

 

 

 

 

 

 

 

Full Load Current

 

Amps

938

782

1083

902

1191

992

(3) Phases, (1) Ground

B

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Conductor Size

 

AWG or kcmil

500

350

500

500

500

500

Number per Phase

 

(each)

(3)

(3)

(4)

(3)

(4)

(4)

 

 

 

 

 

 

 

 

 

AC Input to UPS Bypass (Five Wire)

Full Load Current

(3) Phases, (1) Neutral, (1) Ground

Amps

938

782

1083

902

1191

992

B

Minimum Conductor Size

 

AWG or kcmil

400

500

500

500

500

500

Number per Phase

 

(each)

(4)

(3)

(5)

(4)

(5)

(5)

 

 

 

 

 

 

 

 

 

DC Input from Battery Disconnect to UPS

 

Total Amps

1280

1280

1502

1502

1600

1600

(1) Positive, (1) Negative

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Conductor Size

AWG or kcmil

350

350

500

500

500

500

 

Number per Pole

 

(each)

(6)

(6)

(6)

(6)

(6)

(6)

 

 

 

 

 

 

 

 

 

AC Output to Critical Load (Four Wire)

 

 

 

 

 

 

 

 

Full Load Current

 

Amps

938

782

1083

902

1191

992

(3) Phases, (1) Ground

D

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Conductor Size

 

AWG or kcmil

500

350

500

500

500

500

Number per Phase

 

(each)

(3)

(3)

(4)

(3)

(4)

(4)

 

 

 

 

 

 

 

 

 

AC Output to Critical Load (Five Wire)

Full Load Current

(3) Phases, (1) Neutral, (1) Ground

Amps

938

782

1083

902

1191

992

D

Minimum Conductor Size

 

AWG or kcmil

400

500

500

500

500

500

Number per Phase

 

(each)

(4)

(3)

(5)

(4)

(5)

(5)

 

 

 

 

 

 

 

 

 

Neutral Bonding Jumper (Four Wire Output Only)

 

 

 

 

 

 

 

 

Minimum Conductor Size

AWG or kcmil

4/0

4/0

4/0

4/0

4/0

4/0

Number

 

(each)

(1

(1)

(1

(1)

(1

(1)

NOTE Callout letters A, B, C, and D map to Figure 6-5, Figure 6-7, Figure 6-9,or Figure 6-11starting on page 6−8.