UPS INSTALLATION PLAN AND UNPACKING

Table 3-5. Input/Output Ratings and External Wiring Requirements for the Powerware 9395−825/650, 9395−825/750, and 9395−825/825

– Separate Battery

 

 

Units

 

 

 

Rating 50/60 Hz

 

 

Basic Unit Rating

 

 

 

 

 

 

 

 

 

kVA

650

650

750

750

825

825

 

 

kW

585

591

675

682

742

750

Input and Output Voltage

 

Volts

400/400

480/480

400/400

480/480

400/400

480/480

 

 

 

 

 

 

 

 

 

AC Input to UPS Rectifier (0.98 Minimum pF)

 

 

 

 

 

 

 

 

Full load current plus battery recharge current

 

Amps

1079

891

1245

1028

1369

1130

(3) Phases, (1) Ground

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Conductor Size

 

AWG or kcmil

500

500

500

500

500

500

Number per Phase

 

(each)

(4)

(3)

(4)

(4)

(5)

(4)

AC Input to UPS Bypass (Four Wire)

 

 

 

 

 

 

 

 

Full Load Current

 

Amps

938

782

1083

902

1191

992

(3) Phases, (1) Ground

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Conductor Size

 

AWG or kcmil

500

350

500

500

500

500

Number per Phase

 

(each)

(3)

(3)

(4)

(3)

(4)

(4)

AC Input to UPS Bypass (Five Wire)

 

 

 

 

 

 

 

 

Full Load Current

 

Amps

938

782

1083

902

1191

992

(3) Phases, (1) Neutral, (1) Ground

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Conductor Size

 

AWG or kcmil

400

500

500

500

500

500

Number per Phase

 

(each)

(4)

(3)

(5)

(4)

(5)

(5)

DC Input from Each Battery Disconnect to Each UPS

 

 

 

 

 

 

 

 

UPM

 

Amps per UPM

551

551

551

551

551

551

(1) Positive, (1) Negative

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Conductor Size

 

AWG or kcmil

250

250

250

250

250

250

Number per Pole

 

(each)

(3)

(3)

(3)

(3)

(3)

(3)

AC Output to Critical Load (Four Wire)

 

 

 

 

 

 

 

 

Full Load Current

 

Amps

938

782

1083

902

1191

992

(3) Phases, (1) Ground

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Conductor Size

 

AWG or kcmil

500

350

500

500

500

500

Number per Phase

 

(each)

(3)

(3)

(4)

(3)

(4)

(4)

AC Output to Critical Load (Five Wire)

 

 

 

 

 

 

 

 

Full Load Current

 

Amps

938

782

1083

902

1191

992

(3) Phases, (1) Neutral, (1) Ground

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Conductor Size

 

AWG or kcmil

400

350

500

500

500

500

Number per Phase

 

(each)

(4)

(3)

(5)

(3)

(5)

(4)

Neutral Bonding Jumper (Four Wire Output Only)

 

 

 

 

 

 

 

 

Minimum Conductor Size

AWG or kcmil

4/0

4/0

4/0

4/0

4/0

4/0

Number

(each)

(1)

(1)

(1)

(1)

(1)

(1)

 

 

 

 

 

 

 

 

 

NOTE Callout letter A,maps to Figure 6-6, Figure 6-8, Figure 6-10,or Figure 6-12starting on page 6−9. Callout letters B, C, and D map to Figure 6-6, Figure 6-8, Figure 6-10, Figure 6-12, Figure 6-13, Figure 6-14, Figure 6-15,or Figure 6-16starting on page 6−9.

3−10

EATON Powerware® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com

Page 32
Image 32
Powerware 650825 kVA AC Input to UPS Bypass Five Wire Full Load Current, DC Input from Each Battery Disconnect to Each UPS