COMMUNICATION

8.9Relay Interface Module II

An optional Relay Interface Module II (RIM II) uses relay contact closures to indicate the operating status and alarm condition of the UPS system. The module uses a serial interface line and may support up to eight critical loads. The RIM II can be flush-mounted or surface-mounted on a desktop, or secured to a wall. Figure 8-4shows the RIM II with its four 15-pin connectors labeled J1 through J4.

Figure 8-4. Relay Interface Module II Customer Interface Connectors J1 through J4

The RIM II can provide the status and alarm signals shown in Table 8-2.

Table 8-2. Customer Interface Connectors

Status

J1 through J4

Description

 

 

 

UPS AVAILABLE

Pins 1 and 12

Contacts are closed when the UPS is operating in Normal mode

 

 

or ready to supply the load.

 

 

 

UPS OFFLINE

Pins 3 and 13

Contacts are open when the UPS is offline.

 

 

Contacts are closed when the UPS is operating in Normal mode.

 

 

 

BATTERY WEAK

Pins 5 and 14

Contacts are closed when approximately two minutes of battery

 

 

time is remaining before the critical load is lost.

 

 

 

UTILITY FAILURE

Pins 6 and 15

Contacts are closed when Utility Failure is detected.

 

 

 