INSTALLING OPTIONS AND ACCESSORIES

Table 5-4. Pull−Chain Wiring Terminations with MOBs

From

To

Function

 

 

 

UPS 1 CAN Bridge Card J3–1 (Alarm)

MOB 1 Aux 1 NC

 

 

 

MOB Open Alarm

UPS 1 CAN Bridge Card J3–2 (Alarm Return)

MOB 1 Aux 1 Com

 

 

 

 

UPS 1 TB2–1 (Pull Chain)

MOB 1 Aux 2 NO

Pull Chain

 

 

 

UPS 1 TB2–2 (Pull Chain Common)

UPS 2 TB2–2 (Pull Chain Common)

Pull Chain Common

 

 

 

 

 

 

UPS 2 CAN Bridge Card J3–1 (Alarm)

MOB 2 Aux 1 NC

 

 

 

MOB Open Alarm

UPS 2 CAN Bridge Card J3–2 (Alarm Return)

MOB 2 Aux 1 Com

 

 

 

 

UPS 2 TB2–1 (Pull Chain)

MOB 2 Aux 2 NO

Pull Chain

 

 

 

UPS 2 TB2–2 (Pull Chain Common)

UPS 3 TB2–2 (Pull Chain Common)

Pull Chain Common

 

 

 

 

 

 

UPS 3 CAN Bridge Card J3–1 (Alarm)

MOB 3 Aux 1 NC

 

 

 

MOB Open Alarm

UPS 3 CAN Bridge Card J3–2 (Alarm Return)

MOB 3 Aux 1 Com

 

 

 

 

UPS 3 TB2–1 (Pull Chain)

MOB 3 Aux 2 NO

Pull Chain

 

 

 

UPS 3 TB2–2 (Pull Chain Common)

UPS 4 TB2–2 (Pull Chain Common)

Pull Chain Common

 

 

 

 

 

 

UPS 4 CAN Bridge Card J3–1 (Alarm)

MOB 4 Aux 1 NC

 

 

 

MOB Open Alarm

UPS 4 CAN Bridge Card J3–2 (Alarm Return)

MOB 4 Aux 1 Com

 

 

 

 

UPS 4 TB2–1 (Pull Chain)

MOB 4 Aux 2 NO

Pull Chain

 

 

 

 

 

 

MOB 1 Aux 2 Com

MOB 2 Aux 2 Com

 

 

 

 

MOB 2 Aux 2 Com

MOB 3 Aux 2 Com

Pull Chain MOB Common

 

 

 

MOB 3 Aux 2 Com

MOB 4 Aux 2 Com

 

 

 

 

5−8

EATON Powerware® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com

Page 100
Image 100
Powerware 650825 kVA Pull−Chain Wiring Terminations with MOBs, UPS 2 can Bridge Card J3-1 Alarm MOB 2 Aux 1 NC