COMMUNICATION

8.5.2Event History Log

This key sequence prints the entire Event History Log of the UPS at the time the data is requested. The printout begins with the oldest alarm entry in the queue and ends with the most recent. Any alarms that occur while the Event History Log is printing are included in chronological order.

The Event History Log lists up to 500 system events in chronological order with the most recent event listed last. Figure 8-2shows a sample Event History Log printout.

In this mode, system events are continually logged through the serial port to the device connected to the port.

The printed log entries contain a time and date stamp and the alarm text message. Terminal mode uses this format for printing alarm entries:

MM DD YYYY

HH:MM:SS.hh KYWD MESSAGE <CR> <LF>

 

 

Where

Equals

 

 

MM

Month (2 digits)

 

 

DD

Day (2 digits)

 

 

YYYY

Year (4 digits)

 

 

HH

Hour (2 digits)

 

 

MM

Minute (2 digits)

 

 

SS

Second (2 digits)

 

 

hh

Hundredths of Second (3 digits)

 

 

KYWD

Keyword (ALARM, NOTICE, COMMAND, or STATUS)

 

 

Message

System Diagnostic Information

 

 

<CR>

Carriage Return Character (ASCII 13)

 

 

<LF>

Line Feed (ASCII 10)

 

 

An alarm message is prefixed by the word

into the Event History Log with a cleared status.

If a port is operating in Terminal mode and is connected to a computer, you can press [Esc] [H] to print the entire log with a firmware version header. The log in Terminal mode is always in English.

EATON Powerware® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com

8−5

Page 175
Image 175
Powerware 650825 kVA operation manual Event History Log