UPS INSTALLATION PLAN AND UNPACKING

AC input to the UPS with separate rectifier inputs is wired as if each UPM is rated for 275 kVA (see Table 3-6). The bypass input, battery input, and output are wired the same as a separate battery UPS (see Table 3-5).

Table 3-6. Separate Rectifier Input UPM Ratings and External Wiring Requirements for the Powerware 9395−825/650, 9395−825/750, and 9395−825/825 – Separate Battery

 

Units

Rating 50/60 Hz

Basic UPM Rating

 

 

 

kVA

275

275

 

kW

247.5

250

 

 

 

 

Input Voltage

Volts

400

480

 

 

 

 

AC Input to each UPM Rectifier (0.98 Min. pF)

 

 

 

Full load current plus battery recharge current

(3) Phases, (1) Ground

Amps 456 370

A

Minimum Conductor Size

AWG or kcmil

2/0

4/0

Number per Phase

(each)

(3)

(2)

 

 

 

 

NOTE Callout letter A, maps to Figure 6-13through Figure 6-16starting on page 6−16.

EATON Powerware® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com