UPS INSTALLATION PLAN AND UNPACKING

Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). See

Table 3-13for conduit requirements.

Per NEC article 300, 3(B)(1), all three-phase conductors must be run in the same conduit. Neutral and ground must be run in the same conduit as the phase conductors.

Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one ground conductor sized in accordance with NEC Table 250.122.

Conduit sizes listed are for copper wiring only.

Table 3-13. Power Cable Conduit Requirements

UPS Model

Voltage

Terminal

Number of Wires

Minimum Conduit

Number of

in Conduit

Trade Size

Conduits

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS Rectifier

4

3

4

 

 

(A, B, C, Ground)

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS Rectifier (Separate Feed)

4

2

3

 

 

(A, B, C, Ground)

(Each UPM)

 

 

 

 

 

400 Vac

 

 

 

 

 

AC Input to Bypass and Output (Four Wire)

4

3

3

 

 

 

 

(A, B, C, Ground)

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to Bypass and Output (Five Wire)

5

3

4

 

 

(A, B, C, Neutral, Ground)

 

 

 

 

 

 

 

 

 

 

 

Powerware 9395−825/650

 

AC Input to UPS Rectifier

4

3

3

 

(A, B, C, Ground)

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS Rectifier (Separate Feed)

4

2

2

 

 

(A, B, C, Ground)

(Each UPM)

 

 

 

 

 

480 Vac

 

 

 

 

 

AC Input to Bypass and Output (Four Wire)

4

2-1/2

3

 

 

 

 

(A, B, C, Ground)

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to Bypass and Output (Five Wire)

5

3

4

 

 

(A, B, C, Neutral, Ground)

 

 

 

 

 

 

 

 

 

 

 

 

DC

Battery

 

See Note

 

 

(Positive, Negative, Ground)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS Rectifier

4

3

4

 

 

(A, B, C, Ground)

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS Rectifier (Separate Feed)

4

2

3

 

 

(A, B, C, Ground)

(Each UPM)

 

 

 

 

 

400 Vac

 

 

 

 

 

AC Input to Bypass and Output (Four Wire)

4

3

4

 

 

 

 

(A, B, C, Ground)

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to Bypass and Output (Five Wire)

5

3

5

 

 

(A, B, C, Neutral, Ground)

 

 

 

 

 

 

 

 

 

 

 

Powerware 9395−825/750

 

AC Input to UPS Rectifier

4

3

4

 

(A, B, C, Ground)

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS Rectifier (Separate Feed)

4

2

2

 

 

(A, B, C, Ground)

(Each UPM)

 

 

 

 

 

480 Vac

 

 

 

 

 

AC Input to Bypass and Output (Four Wire)

4

3

3

 

 

 

 

(A, B, C, Ground)

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to Bypass and Output (Five Wire)

5

3

4

 

 

(A, B, C, Neutral, Ground)

 

 

 

 

 

 

 

 

 

 

 

 

DC

Battery

 

See Note

 

 

(Positive, Negative, Ground)

 

 

 

 

 

 

 

 

 

 

 

 

 

EATON Powerware® 9395 UPS (650–825 kVA) Installation and Operation Manual S 164201725 Rev 2 www.powerware.com

3−15

Page 37
Image 37
Powerware 650825 kVA Power Cable Conduit Requirements, UPS Model Voltage Terminal Number of Wires Minimum Conduit