Chapter 5

Installing Options and Accessories

5.1Installing an Optional Powerware Hot Sync CAN Bridge Card

As an option, a Powerware Hot Sync Controller Area Network (CAN) Bridge Card, shown in Figure 5-1,can be installed to provide connectivity for operational mode control of a parallel system. In addition, this card can be used to connect optional system monitoring devices, such as a Remote Monitor Panel II, a Relay Interface Module II, or a Supervisory Contact Module II to the UPS.

Plug−in Terminal

Block J3

Figure 5-1. Powerware Hot Sync CAN Bridge Card

NOTE Only one Powerware Hot Sync CAN Bridge Card can be installed in the UPS. Multiple CAN cards are not supported and will cause system conflicts.

To install the card:

1.Verify the UPS system is turned off and all power sources are removed. See Chapter 7,

2.Unfasten the front door latch and swing the door open (see Figure 4-1on page 4−2).

3.Install the Powerware Hot Sync CAN Bridge Card into an open X−Slot communication bay on the front of the UPS. See Figure 4-27on page 4−32 and Figure 4-33on page 4−38 for X−Slot communication bay locations.