Cisco Systems Cisco uBR10012 manual Site Requirements

Models: Cisco uBR10012

1 304
Download 304 pages 40.3 Kb
Page 76
Image 76

Chapter 2 Preparing for Installation

Site Requirements

Follow these basic guidelines when you are working with any electrical equipment:

Before beginning any procedures requiring access to the chassis interior, locate the emergency power-off switch for the room in which you are working.

Disconnect all power and external cables before installing or removing a chassis.

Do not work alone when potentially hazardous conditions exist.

Never assume that power has been disconnected from a circuit; always check.

Do not perform any action that creates a potential hazard to people or makes the equipment unsafe. Never install equipment that appears damaged.

Carefully examine your work area for possible hazards such as moist floors, ungrounded power extension cables, and missing safety grounds.

Warning When installing or replacing the unit, the ground connection must always be made first and disconnected last. Statement 1046

Warning Do not work on the system or connect or disconnect cables during periods of lightning activity. Statement 1001

Warning Read the installation instructions before you connect the system to its power source. Statement 1004

Site Requirements

This section provides information for environmental, power, cabling, and rack mounting requirements. Be sure that you have met all of these requirements before you install your Cisco uBR10012 router.

Caution The Cisco uBR10012 router installation must comply with all applicable codes and is approved for use with copper conductors only. The ground bond fastening hardware should be of compatible material and preclude loosening, deterioration, and electrochemical corrosion of hardware and joined material.

Attachment of the chassis ground to a central office or other interior ground system should be made with a 6-AWG, copper ground conductor at a minimum.

Warning This unit is intended for installation in restricted access areas. A restricted access area can be accessed only through the use of a special tool, lock and key, or other means of security. Statement 1017

Cisco uBR10012 Universal Broadband Router Hardware Installation Guide

2-4

OL-18259-01

 

 

Page 76
Image 76
Cisco Systems Cisco uBR10012 manual Site Requirements