Chapter 5 Maintaining the Cisco uBR10012 Router

Removing and Replacing AC PEM Modules

Figure 5-23 Turning the AC PEM Off

ALARMS

ACO

CRITICAL MAJOR

MINOR

STATUS

FAIL

PERFORMANCE ROUTING ENGINE

ALARMS

ACO

CRITICAL M AJOR

MINOR

STATUS

FAIL

PERFORMANCE ROUTING ENGINE

 

AC

 

SWITCH

 

AC

ACINPUT

SWITCH

200-240V

 

13A 50/60Hz

 

 

ACINPUT

 

200-240V

 

13A 50/60Hz

AC

SWITCH

ACINPUT

200-

13A

240V

50/60Hz

 

77142

Step 3 Unplug the AC-input power cable from the power plug on the front panel of each AC PEM. For safety, also unplug the other end of the power cable from each AC-input power source.

Tip For true redundant power protection, ensure that you are using a separate AC-input power source for each AC PEM.

Step 4 Use the screwdriver to loosen the captive screws on each AC PEM. Then pull each AC PEM from the chassis by using the handle on the faceplate (see Figure 5-19). Set the two AC PEMs aside.

Step 5 Verify that the power switch on each replacement AC PEM is in the standby position (see Figure 5-23).

Step 6 Position the first replacement AC PEM in the power bay and push it forward. Verify that it goes all the way in and makes a secure connection with the backplane.

Step 7 Use the screwdriver to tighten the captive screws to secure the unit to the chassis.

Step 8 Position the second replacement AC PEM in the power bay and push it forward. Verify that it goes all the way in and makes a secure connection with the backplane.

Step 9 Tighten the captive screws to secure the unit to the chassis (see Figure 5-20).

Caution Although one AC PEM can supply sufficient power for a fully configured chassis, run the

Cisco uBR10012 router with two AC PEMs installed, because this provides redundant power support.

Step 10 Plug the AC-input power cable into the power receptacle on the front panel of each AC PEM.

Step 11 Route the power cable up the front of the AC PEM and clip it into the two plastic retaining clips attached to the surface of the PEM. Route the power cable out through the right side, so that it fits through the notch on the right side of the front bezel cover, see Figure 5-21.

Step 12 Plug the other end of the AC-input power cable into a 200–240 VAC power outlet. For fully redundant operation, each AC PEM should use separate power sources, or you should be using an uninterruptible power supply (UPS).

 

 

Cisco uBR10012 Universal Broadband Router Hardware Installation Guide

 

 

 

 

 

 

OL-18259-01

 

 

5-27

 

 

 

 

 