Cisco Systems Cisco uBR10012 Installing the PEM in the Chassis, Alarm Terminal Block Connections

Models: Cisco uBR10012

1 304
Download 304 pages 40.3 Kb
Page 184
Image 184

Chapter 5 Maintaining the Cisco uBR10012 Router

Connecting Alarm Indicators

Step 5 Secure the cabling to the chassis by feeding a tie wrap through one of the round holes next to the large hole on the side of the chassis. Then use the tie wrap to bind the cables to the chassis.

Figure 5-17 Alarm Terminal Block Connections

MINOR

MAJOR

NC COM NO

CRITICAL

ALARMS

NC COM NO

NC COM NO

60 VDC

 

1A MAX

 

MINOR

NC COM NO

98749

Installing the PEM in the Chassis

Step 1 Position the DC PEM in the power bay and push it forward, verifying that it goes all the way in and makes a secure connection with the backplane (see Figure 5-14).

Step 2 Tighten the captive screws on the DC PEM to lock it into the chassis.

Step 3 Turn on the DC power source that are providing power for DC PEM.

Tip The FAULT LED on each replacement DC PEM lights (yellow) to indicate that the DC PEM is receiving power from the power source but that it is not yet supplying power to the Cisco uBR10012 chassis.

Step 4 Push up the power switch on each DC PEM to the on () position (see Figure 5-10).

Step 5 When you turn on the power switch on each DC PEM, its FAULT LED turns off and the POWER LED lights (green).

Step 6 Replace the front cover (see the “Replacing the Front Cover” section on page 5-4).

 

Cisco uBR10012 Universal Broadband Router Hardware Installation Guide

5-20

OL-18259-01

Page 184
Image 184
Cisco Systems Cisco uBR10012 manual Installing the PEM in the Chassis, Alarm Terminal Block Connections