Reference Manual

00809-0100-4663, Rev BA January 2010

Rosemount 8732

Table B-6. Sensor Approval Information

SPECIAL CONDITIONS FOR SAFE USE (KEM 07.0038X):

If the Rosemount 8732 Flow Transmitter is used integrally with the Rosemount 8705 or 8711 Sensors, it shall be assured that the mechanical contact areas of the Sensor and Flow Transmitter comply with the requirements for flat joints according to standard EN/IEC 60079-1 clause 5.2.

The relation between ambient temperature, process temperature, and temperature class is to be taken from Table B-8 on page B-13

The electrical data is to be taken from Table B-7 on page B-12

If the Rosemount 8732 Flow Transmitter is used integrally with the Junction Box, it shall be assured that the mechanical contact areas of the Junction Box and Flow Transmitter comply with the requirements for flanged joints according to standard EN/IEC 60079-1 clause 5.2.

INSTALLATION INSTRUCTIONS:

The cable and conduit entry devices and blanking elements shall be of a certified flameproof type, suitable for the conditions of use and correctly installed. With the use of conduit, a certified stopping box shall be provided immediately to the entrance of the enclosure.

N7 IECEx Type n

8712D - Certificate No: IECEx BAS 07.0036X

EEx nA nL IIC T4 (Ta = -50 °C to + 60 °C) Vmax = 42 V DC

8732 - Certificate No: IECEx BAS 07.0062X

Ex nA nL IIC T4 (Ta = -50 °C to + 60 °C) Vmax = 42 V DC

Remote Junction Box

8732 - Certificate No.: KEM 07.0038X IECEx Ex e (1) T6 (Ta = -50 °C to + 60 °C) When installed per drawing 08732-1060

After de-energizing, wait 10 minutes before opening cover

(1)IIC for E7 IIB for EF

 

 

 

 

 

 

 

 

 

Rosemount 8705 Sensor

Rosemount 8707 Sensor

Rosemount 8711 Sensor

Rosemount 8721

 

Sensors

 

For

For

For

For

For

For

For

Approval

Non-flammable Flammable Non-flammable Flammable Non-flammable Flammable

Non-flammable

Codes

Fluids

Fluids

Fluids

Fluids

Fluids

Fluids

Fluids

NA

 

 

 

 

 

N0

 

 

 

 

ND

N1

 

 

 

N5

 

N7

 

 

 

ND

 

 

 

NF

 

 

 

E1

 

 

 

E5(1)

 

 

 

KD(2)

 

 

 

 

 

(1)Available in line sizes up to 8 in. (200 mm) only.

(2)Refer to Table B-8 on page B-13for relation between ambient temperature, process temperature, and temperature class.