Rosemount 8732
Reference Manual
00809-0100-4663, Rev BA January 2010
Rosemount 8721 Sanitary Magmeter Sensors in line sizes of 11/2 in. and larger:
Module A Conformity Assessment
All other Rosemount 8705/8707/8711/8721 Sensors —
in line sizes of 1 in. and less: Sound Engineering Practice
Sensors that are SEP are outside the scope of PED and cannot be marked for compliance with PED.
Mandatory
Sensor category I is assessed for conformity per module A procedures. Sensor categories II – IV, use module H for conformity assessment procedures.
Electro Magnetic Compatibility (EMC) (2004/108/EC)
Models 8712D - EN
Model 8732E - EN 61326: 1997: A1 + A2 + A3
Installed signal wiring should not be run together and should not be in the same cable tray as AC power wiring.
Device must be properly grounded or earthed according to local electric codes. To improve protection against signal interference, shielded cable is recommended.
Low Voltage Directive (93/68/EEC)
Model 8712D - EN 61010
Low Voltage Directive (2006/95/EC)
Model 8732E - EN 61010
Other important guidelines
Only use new, original parts.
To prevent the process medium escaping, do not unscrew or remove process flange bolts, adapter bolts or bleed screws during operation.
Maintenance shall only be done by qualified personnel.
CE CE Marking
Compliance with all applicable European Union Directives. (Note: CE Marking is not available on Rosemount 8712H).
IECEx Scheme
For Rosemount 8732E transmitters:
Rosemount complies with all of the stated standards below:
IEC
IEC
IEC
IEC
IEC
IEC
IEC
IEC
Complies with IEC