Reference Manual

00809-0100-4663, Rev BA January 2010

Rosemount 8732

RESOURCE BLOCK ERRORS

Table F-2. Resource BLOCK_ERR Conditions

Table F-2lists conditions reported in the BLOCK_ERR parameter. Conditions in italics are inactive for the resource block and are given here only for your reference.

Condition

 

Number

Condition Name and Description

 

 

1

Block Configuration Error: A feature in FEATURES_SEL is set that is

 

not supported by FEATURES or an execution cycle in CYCLE_SEL is

 

set that is not supported by CYCLE_TYPE.

 

 

2

Link Configuration Error: A link used in one of the function blocks is

 

improperly configured.

3

Simulate Active: The simulation jumper is in place. Simulate active is

 

not an indication that the I/O blocks are using simulated data.

 

 

4

Local Override

5

Device Fault State Set

 

 

6

Device Needs Maintenance Soon

7

Input failure/process variable has bad status

 

 

8

Output Failure: The output is bad based primarily upon a bad input.

9

Memory Failure: A memory failure has occurred in FLASH, RAM, or

 

EEPROM memory.

 

 

10

Lost Static Data: Static data that are stored in nonvolatile memory have

 

been lost.

11

Lost NV Data: Nonvolatile data that are stored in nonvolatile memory

 

have been lost.

 

 

12

Readback Check Failed

13

Device Needs Maintenance Now

 

 

14

Power Up: The device was just powered-up.

15

Out of Service: The actual mode is out of service.

 

 

MODES

The resource block supports two modes of operation as defined by the

 

MODE_BLK parameter:

 

Automatic (Auto)—The block is processing its normal background

 

memory checks.

 

Out of Service (O/S)—The block is not processing its tasks. When the

 

resource block is in O/S, all blocks within the resource (device) are

 

forced into O/S. The BLOCK_ERR parameter shows OUT OF

 

SERVICE. In this mode, you can make changes to all configurable

 

parameters. The target mode of a block may be restricted to one or

 

more of the supported modes.

F-5

Page 171
Image 171
Emerson Process Management 8732 manual Resource Block Errors, Modes