Reference Manual

00809-0100-4663, Rev BA January 2010

Rosemount 8732

Figure 2-1. Rosemount 8732 Dimensional Drawing

 

 

7.49 (190)

 

 

 

6.48 (165)

LOI Cover

 

 

 

4.97

3.00

 

1/2”-14 NPT Electrical

(126)

(76)

 

Conduit Connections

 

(2 places with a 3rd

8.81

 

 

optional)

(224)

 

 

1/2”-14 NPT Remote Junction

 

 

 

 

 

 

Box Conduit Connections (2

 

3.07

 

places)

 

(78)

 

 

 

 

4.97

 

 

 

(126)

 

 

 

 

5.82

 

 

 

(148)

ENVIRONMENTAL CONSIDERATIONS

To ensure maximum transmitter life, avoid temperature extremes and vibration. Typical problem areas include:

high-vibration lines with integrally mounted transmitters

warm-climate installations in direct sunlight

outdoor installations in cold climates.

INSTALLATION

PROCEDURES Mount the Transmitter

Remote-mounted transmitters may be installed in the control room to protect the electronics from a harsh environment and provides easy access for configuration or service.

Rosemount 8732 transmitters require external power so there must be access to a suitable power source.

Rosemount 8732 installation includes both detailed mechanical and electrical installation procedures.

Remote-mounted transmitters may be mounted on a pipe up to two inches in diameter or against a flat surface.

Pipe Mounting

To mount the transmitter on a pipe:

1.Attach the mounting bracket to the pipe using the mounting hardware.

2.Attach the 8732 to the mounting bracket using the mounting screws.