Reference Manual

00809-0100-4663, Rev BA January 2010

Rosemount 8732

Taylor Sensor to Rosemount 8732 Transmitter

Connect coil drive and electrode cables as shown in Figure E-20.

Figure E-20. Generic Wiring Diagram for Taylor Sensors and Rosemount 8732

Table E-21. Taylor Sensor Wiring Connections

 

TAYLOR

ROSEMOUNT 8732

 

SENSORS

TRANSMITTER

 

 

E2

Electrodes

 

E1

 

S1 and S2

 

Green

Coils

White

 

 

Black

 

 

Fuse

Rosemount 8732

 

Taylor Sensors

1

 

 

 

Black

2

 

 

 

White

 

 

 

 

 

 

Green

 

 

 

 

 

17

 

 

S1 and S2

18

 

 

E1

19

 

 

E2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This is a pulsed DCDC magnetic flowmeter. Do not connect AC power to the sensor or to terminals 1 and 2 of the transmitter, or replacement of the electronics board will be necessary.

E-23

Page 163