Rosemount 8732
Problems in the magnetic flowmeter system are usually indicated by incorrect output readings from the system, error messages, or failed tests. Consider all sources in identifying a problem in your system.
Table
Message | Potential Cause | Corrective Action |
|
|
|
“Fieldbus Not | Fieldbus segment is disconnected | Connect the fieldbus segment |
Communicating” | Fieldbus segment power missing | Verify the segment fieldbus voltage |
| Electronics failure | Replace electronics |
“Sensor Processor Not | Transmitter input power (AC/DC) is | Connect the input power. If the LCD displays a message, the input power is |
Communicating” | not connected | applied |
| Electronics failure | Replace electronics |
“Empty Pipe” | Empty Pipe | None - message will clear when pipe is full |
| Wiring Error | Check that wiring matches appropriate wiring diagrams - see Appendix E: |
|
| Universal Sensor Wiring Diagrams |
| Electrode Error | Perform sensor tests C and D (see Table |
| Conductivity less than 5 | Increase Conductivity to greater than or equal to 5 microsiemens per cm |
| microsiemens per cm |
|
| Intermittent Diagnostic | Adjust tuning of Empty Pipe parameters |
“Coil Open Circuit” | Improper wiring | Check coil drive wiring and sensor coils |
|
| Perform sensor test A - Sensor Coil |
| Other manufacturer’s sensor | Change coil current to 75 mA |
|
| Perform a Universal Auto Trim to select the proper coil current |
| Circuit Board Failure | Replace Rosemount 8732 Electronics |
| Coil Circuit OPEN Fuse | Return to factory for fuse replacement |
“Auto Zero Failure” | Flow is not set to zero | Force flow to zero, perform autozero |
(Cycle power to clear | Unshielded cable in use | Change wire to shielded cable |
messages, no changes | Moisture problems | See moisture problems in “Accuracy Section” |
were made) | Empty pipe is present | Fill sensor with process fluid |
“Universal Trim Failure” | No flow in pipe while performing | Establish a known flow in sensor, and perform Universal |
| Universal Auto Trim | calibration |
| Wiring error | Check that wiring matches appropriate wiring diagrams - see “Universal |
|
| Sensor Wiring Diagrams” on page |
| Flow rate is changing in pipe while | Establish a constant flow in sensor, and perform Universal |
| performing Universal | calibration |
| routine |
|
| Flow rate through sensor is | Verify flow in sensor and perform Universal |
| significantly different than value |
|
| entered during Universal |
|
| routine |
|
| Incorrect calibration number | Replace sensor calibration number with 1000005010000001 |
| entered into transmitter for |
|
| Universal |
|
| Wrong sensor size selected | Correct sensor size setting - See “Line Size” on page |
| Sensor failure | Perform sensor tests C and D (see Table |
“Electronics Failure” | Electronics self check failure | Replace Electronics |
|
|
|
“Electronics Temp Fail” | Ambient temperature exceeded the | Move transmitter to a location with an ambient temperature range of |
| electronics temperature limits | 165 °F |
“Reverse Flow” | Electrode or coil wires reverse | Verify wiring between sensor and transmitter |
| Flow is reverse | Turn ON Reverse Flow Enable to read flow |
| Sensor installed backwards | |
|
| or the coil wires (1 and 2) |
“Flow Rate > Sensor Limit” | Flow rate is greater than 43 ft/sec | Lower flow velocity, increase pipe diameter |
| Improper wiring | Check coil drive wiring and sensor coils |
|
| Perform sensor test A - Sensor Coil (see Table |
“Digital Trim Failure” | The calibrator (8714B/C/D) is not | Review calibrator connections |
(Cycle power to clear | connected properly |
|
messages, no changes | Incorrect calibration number | Replace sensor calibration number with 1000005010000001 |
were made) | entered into transmitter |
|
| Calibrator is not set to 30 FPS | Change calibrator setting to 30 FPS |
| Bad calibrator | Replace calibrator |
|
|