Reference Manual
00809-0100-4663, Rev BA
January 2010
Rosemount 8732
6-8
To test the sensor, a multimeter capable of measuring conductance in nanosiemens is preferred. Nanosiemens is the reciprocal of resistance. or Table 6-5. Sensor Test
Test Sensor
Location Required
Equipment Measuring at
Connections Expected Value Potential Cause Corrective Action
A. Sensor
Coil Installed or
Uninstalled Multimeter 1 and 2 = R Open or
Shorted Coil Remove and
replace sensor
B. Shields to
Case Installed or
Uninstalled Multimeter 17 and
and case
ground
17 and case
ground
Moisture in
terminal block
Leaky electrode
Process behind
liner
Clean terminal
block
Remove sensor
C. Coil Shield
to Coil Installed or
Uninstalled Multimeter 1 and
2 and
(< 1nS)
(< 1nS) Process behind
liner
Leaky electrode
Moisture in
terminal block
Remove sensor
and dry
Clean terminal
block
Confirm with
sensor coil test
D. Electrode
Shield to
Electrode
Installed LCR (Set to
Resistance
and 120 Hz)
18 and 17 = R1
19 and 17 = R2
R1 and R2 should be stable
NO:
N5, E5, CD,
ED:
Unstable R1 or
R2 values
confirm coated
electrode
Shorted
electrode
Electrode not in
contact with
process
Empty Pipe
Low conductivity
Leaky electrode
Remove coating
from sensor wall
Use bulletnose
electrodes
Repeat
measurement
Pull sensor,
complete test in
Table6-6 and
Table 6-7 on
page6-10 out of
line.
2R18
0.2


R1R2300
R1R21500
1nanosiemens 11gigaohm----------------------------=
1nanosiemens 11109ohm
-------------------------------=