Reference Manual

00809-0100-4663, Rev BA January 2010

Rosemount 8732

Device Info

375Transducer Block, Detailed

Setup

For example, if the number of samples selected is 100, then the response time of the system is 10 seconds. In some cases this may be unacceptable. By setting the time limit, you can force the 8732E to clear the value of the running average and re-establish the output and average at the new flow rate once the time limit has elapsed. This parameter limits the response time added to the loop. A suggested time limit value of two seconds is a good starting point for most applicable process fluids. The selected signal processing configuration may be turned ON or OFF to suit your needs.

Coil Drive Frequency

375 Transducer Block, Detailed Setup, Signal Processing

Coil drive frequency allows pulse-rate selection of the sensor coils.

5 Hz

The standard coil drive frequency is 5 Hz, which is sufficient for nearly all applications.

37 Hz

If the process fluid causes a noisy or unstable output, increase the coil drive frequency to 37 Hz. If the 37 Hz mode is selected, perform the auto zero function with no flow and a full sensor.

Low Flow Cutoff

375 Transducer Block, Detailed Setup, Signal Processing

Low flow cutoff allows you to specify the flow rate, between 0.01 and 38.37 feet per second, below which the outputs are driven to zero flow. The units format for low flow cutoff cannot be changed. It is always displayed as feet per second regardless of the format selected. The low flow cutoff value applies to both forward and reverse flows.

Primary Variable Damping

375 Transducer Block, Detailed Setup, Signal Processing

0 to 256 Seconds

Primary Variable Damping allows selection of a response time, in seconds, to a step change in flow rate. It is most often used to smooth fluctuations in output.

Information variables are used for identification of flowmeters in the field and to store information that may be useful in service situations. Information variables have no effect on flowmeter output or process variables.

Device ID

375 Transducer Block, Detailed Setup, Device Info

This function displays the Device ID of the transmitter. This is one piece of information required to generate a license code to enable diagnostics in the field.

PV Sensor S/N

375 Transducer Block, Detailed Setup, Device Info

The PV sensor serial number is the serial number of the sensor connected to the transmitter and can be stored in the transmitter configuration for future reference. The number provides easy identification if the sensor needs servicing or for other purposes.

4-15

Page 53
Image 53
Emerson Process Management 8732 manual Device Info, Low Flow Cutoff, Primary Variable Damping, PV Sensor S/N