Series 1800 (Version 2) Sensor to Rosemount 8732 Transmitter

Connect coil drive and electrode cables as shown in Figure E-13.

Figure E-13. Wiring Diagram for Foxboro Series 1800 (Version 2) and Rosemount 8732

Table E-14. Foxboro Generic Sensor Wiring Connections

FOXBORO SERIES

 

ROSEMOUNT

1800 SENSOR

 

8732

(VERSION 2)

 

TRANSMITTER

 

 

White

 

 

Black

 

 

Shield

Electrode

 

 

Connections

 

 

GND

L2

L1

 

Coil Connections

Rosemount 8732

 

Foxboro Series 1800 Sensors

1

 

 

 

L1

2

 

 

 

L2

 

 

 

 

 

 

Chassis Ground

 

 

 

 

 

17

 

 

Any Shield

18

 

 

Black

19

 

 

White

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This is a pulsed DC magnetic flowmeter.

Do not connect AC power to the sensor or to terminals 1 and 2 of the transmitter, or replacement of the electronics board will be necessary.