Emerson Process Management 8732 manual Perform the auto zero function with full pipe and no flow

Models: 8732

1 190
Download 190 pages 62.1 Kb
Page 80
Image 80

Rosemount 8732

Reference Manual

00809-0100-4663, Rev BA January 2010

Table 6-4. Advanced Troubleshooting–Rosemount 8732

Symptom

Potential Cause

 

Corrective Action

 

 

 

Meter output is unstable

Medium to low conductivity fluids (10–

Eliminate cable vibration:

 

25 microsiemens/cm) combined with

Integral mount

 

cable vibration or 60 Hz interference

Move cable to lower vibration run

 

 

Tie down cable mechanically

 

 

Trim electrode and coil wires

 

 

• See “Conduit Cables” on page 2-6

 

 

Route cable line away from other equipment

 

 

 

powered by 60 Hz

 

 

Use 8712-0752-1,3 cable

 

Electrode incompatibility

Check the Technical Data Sheet, Magnetic Flowmeter Material

 

 

Selection Guide (document number 00816-0100-3033), for

 

 

chemical compatibility with electrode material.

 

Improper grounding

Check ground wiring – see “Mount the Transmitter” on page 2-3

 

 

for wiring and grounding procedures

 

High local magnetic or electric fields

Move magnetic flowmeter (20–25 ft away is usually acceptable)

 

Control loop improperly tuned

Check control loop tuning

 

Sticky valve (look for periodic

Service valve

 

oscillation of meter output)

 

 

 

Sensor failure

Perform the sensor Tests A, B, C, and D

 

 

(See Table 6-5 on page 6-8)

Reading does not appear to be

Transmitter, control system, or other

Check all configuration variables for the transmitter, sensor,

within rated accuracy

receiving device not configured

communicator, and/or control system

 

properly

Check these other transmitter settings:

 

 

 

 

Sensor calibration number

 

 

Units

 

 

Line size

 

Electrode coating

Use bulletnose electrodes in the Rosemount 8705 Sensor.

 

 

Downsize the sensor to increase the flow rate above 3 ft/s.

 

 

Periodically clean the sensor

 

Air in line

Move the sensor to another location in the process line to

 

 

ensure that it is full under all conditions

 

Flow rate is below 1 ft/s

See the accuracy specification for specific transmitter and

 

(specification issue)

sensor

 

Insufficient upstream/downstream

Move sensor to location where 5 pipe diameters upstream and 2

 

pipe diameter

pipe diameters downstream is possible

 

Cables for multiple magmeters run

Run only one conduit cable between each sensor and

 

through same conduit

transmitter

 

Auto zero was not performed when the

Perform the auto zero function with full pipe and no flow

 

coil drive frequency was changed from

 

 

 

5 Hz to 37.5 Hz

 

 

 

Sensor failure—shorted electrode

See Table 6-5 on page 6-8

 

Sensor failure—shorted or open coil

See Table 6-5 on page 6-8

 

Transmitter failure

Replace the electronics board

 

Transmitter wired to correct sensor

Check wiring

6-6

Page 80
Image 80
Emerson Process Management 8732 manual Perform the auto zero function with full pipe and no flow