Reference Manual

00809-0100-4663, Rev BA January 2010

Rosemount 8732

Appendix F Resource Block

 

Parameters and Descriptions

page F-1

 

Resource Block Errors

page F-5

 

Modes

page F-5

 

Troubleshooting

page F-6

 

This section contains information on the resource block for the

 

Rosemount 8732 Magnetic Flowmeter Transmitter. Descriptions of all

 

resource block parameters, errors, and diagnostics are included. Also, the

 

modes, alarm detection, status handling, virtual communication relationships

 

(VCRs), and troubleshooting are discussed.

 

Definition

The resource block defines the physical resources of the device, such as

 

measurement and memory. The resource block also handles functionality,

 

such as shed times, that is common across multiple blocks. The block has no

 

linkable inputs or outputs, and it performs memory-level diagnostics.

PARAMETERS AND DESCRIPTIONS

Table F-1. Resource Block Parameters

Table F-1lists all of the configurable parameters of the resource block, including the descriptions and index numbers for each parameter. Newer software revisions have added functionality and some index numbers have changed. To determine the software revision of a transmitter, check the parameter SOFTWARE_REVISION_MAJOR. The most recent transmitters have a label on the electronic board stack.

 

Index Number

 

Parameter

Rev 5

Description

ACK_OPTION

38

ACK_OPTION is a selection of whether alarms associated with the function block

 

 

will be automatically acknowledged.

ADVISE_ACTIVE

82

Active advisory alarms.

ADVISE_ALM

83

Alarm indicating advisory alarms. These conditions do not have a direct impact on

 

 

the process or device integrity.

ADVISE_ENABLE

80

Enables or disables the advisory conditions within a device.

ADVISE_MASK

81

Mask of advisory Alarm. Corresponds bit for bit to the Advisory Active. A bit on

 

 

means that the failure is masked out from alarming.

ADVISE_PRI

79

Designates the alarming priority of the advisory alarm.

ALARM_SUM

37

This parameter shows the current alert status, unacknowledged states, unreported

 

 

states, and disabled states of the alarms associated with the function block. In the

 

 

Rosemount 8732 Magnetic Flowmeter Transmitter, the two resource block alarms

 

 

are write alarm and block alarm.

ALERT_KEY

04

ALERT_KEY shows the identification number of the plant unit. This information

 

 

may be used in the host for sorting alarms, etc.

www.rosemount.com