Rosemount 8732

Reference Manual

00809-0100-4663, Rev BA January 2010

ADVANCED CONFIGURATION

DETAILED SETUP

375

Transducer Block

In addition to the basic configuration options and the diagnostic information and controls, the 8732 has many advanced functions that can also be configured as required by the application.

The detailed setup function provides access to other parameters within the transmitter that can be configured such as coil drive frequency, output parameters, local display configuration, and other general information about the device.

Additional Parameters

375Transducer Block, Detailed

Setup

The additional parameters menu provides a means to configure optional parameters within the 8732E transmitter.

Coil Drive Frequency

375 Transducer Block, Detailed Setup, Additional Params

Coil drive frequency allows pulse-rate selection of the sensor coils.

5 Hz

The standard coil drive frequency is 5 Hz, which is sufficient for nearly all applications.

37 Hz

If the process fluid causes a noisy or unstable output, increase the coil drive frequency to 37 Hz. If the 37 Hz mode is selected, perform the auto zero function.

Density Value

375 Transducer Block, Detailed Setup, Additional Params

The density value is used to convert from a volumetric flow rate to a mass flow rate using the following equation:

Qm = Qv  Where:

Qm is the mass flow rate

Qv is the volumetric flow rate, and

is the fluid density

NOTE

A density value is required to configure the flow units for mass flow rate measurement.

Sensor Range: EU at 100%

375 Transducer Block, Detailed Setup, Additional Params

This parameter is the maximum value that the PV Range value can be set to. This is the upper measuring limit of the transmitter and sensor.

Sensor Range: EU at 0%

375 Transducer Block, Detailed Setup, Additional Params

This parameter is the minimum value that the PV Range value can be set to. This is the lower measuring limit of the transmitter and sensor.

4-12

Page 50
Image 50
Emerson Process Management 8732 manual Advanced Configuration Detailed Setup, Additional Parameters