Rosemount 8732

Reference Manual

00809-0100-4663, Rev BA January 2010

Alarm Detection

A block alarm will be generated whenever the BLOCK_ERR has an error bit set. The types of block error for the resource block are defined in Table F-2.

A write alarm is generated whenever the WRITE_LOCK parameter is cleared. The priority of the write alarm is set in the following parameter:

WRITE_PRI

Alarms are grouped into five levels of priority, as shown in Table F-3.

Table F-3. Alarm Priorities

Priority

 

Number

Priority Description

 

 

0

The priority of an alarm condition changes to 0 after the condition that

 

caused the alarm is corrected.

 

 

1

An alarm condition with a priority of 1 is recognized by the system, but is

 

not reported to the operator.

2

An alarm condition with a priority of 2 is reported to the operator, but

 

does not require operator attention (such as diagnostics and system

 

alerts).

 

 

3–7

Alarm conditions of priority 3–7 are advisory alarms of increasing

 

priority.

8–15

Alarm conditions of priority 8–15 are critical alarms of increasing priority.

 

 

Status Handling

VCR

There are no status parameters associated with the resource block.

The number of configurable virtual communication relationships or VCRs is

18.The parameter is not contained or viewable within the resource block, but it does apply to all blocks.

TROUBLESHOOTING

Refer to Table F-4to troubleshoot resource block problems.

Table F-4. Troubleshooting

 

 

 

 

 

 

 

 

 

 

 

Symptom

Possible Causes

Corrective Action

 

 

 

 

 

 

 

Mode will not

Target mode not set

Set target mode to something other

 

 

leave OOS.

 

than OOS.

 

 

 

 

 

 

 

 

Memory failure

BLOCK_ERR will show the lost NV

 

 

 

 

Data or Lost Static Data bit set.

 

 

 

 

Restart the device by setting

 

 

 

 

RESTART to Processor. If the block

 

 

 

 

error does not clear, call the factory.

 

 

Block alarms will

Features

FEATURES_SEL does not have

 

 

not work.

 

Alerts enabled. Enable the Alerts bit.

 

 

 

 

 

 

 

 

Notification

LIM_NOTIFY is not high enough. Set

 

 

 

 

equal to MAX_NOTIFY.

 

 

 

Status options

STATUS_OPTS has Propagate Fault

 

 

 

 

Forward bit set. This should be

 

 

 

 

cleared to cause an alarm to occur.

 

 

 

 

 