Installing the Hardware

Internally, the X-Pedition 8600 DC power supply consists of two separate power supplies. Each of these internal power supplies must be energized to produce sufficient power for the

X-Pedition 8600 to operate. Each internal power supply is connected to source power through a pair of positive (+) and negative (-) wiring lugs on the wiring block. Figure 27 shows the internal relationship of the wiring lugs of the X-Pedition 8600 DC power supply.

XP-8600 DC Power Supply

Internal Power Supply One

These lugs supply power to Power Supply One

These lugs supply power to Power Supply Two

Internal Power Supply Two

Figure 27. Relationship of wiring lugs on X-Pedition 8600 DC power supply

Note: For the X-Pedition 8600 to work properly, both positive (+) terminals and both negative (-) terminals of the X-Pedition 8600 DC power supply MUST be connected to the DC source.

Because of the X-Pedition 8600 DC supply current requirements, each pole of the 48 Volt DC source should use 6 gauge wire. Each 6 gauge wire can be divided into two 12 gauge wires by using a conductive splitter-block. This creates two 12 gauge wires carrying positive (+) current and two 12 gauge wires carrying negative current. In turn, both 12 gauge positive (+) wires and both 12

Enterasys X-Pedition 8000/8600 Getting Started Guide

63