5 20 60 Output frequency
Constant torque B013 = 01
Reduced
torque
B013 = 00

3–31

SJ200 Inverter

 

 

“B” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

 

 

 

 

 

Func.

Name /

 

Description

Mode

–FEF

–FU

 

Units

 

 

 

Edit

 

 

 

Code

SRW Display

(EU)

(USA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B001

Selection of automatic

Select inverter restart method,

00

00

 

 

 

 

restart mode

 

four option codes:

 

 

 

 

 

 

 

 

 

 

00... Alarm output after trip,

 

 

 

 

 

 

 

 

IPS POWR

ALM

 

 

 

 

 

 

 

 

no automatic restart

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01... Restart at 0Hz

 

 

 

 

 

 

 

 

 

 

02... Resume operation after

 

 

 

 

 

 

 

 

 

 

frequency matching

 

 

 

 

 

 

 

 

 

 

03... Resume previous freq.

 

 

 

 

 

 

 

 

 

 

after freq. matching, then

 

 

 

 

 

 

 

 

 

 

decelerate to stop and display

 

 

 

 

 

 

 

 

 

 

trip info.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B002

Allowable under-

The amount of time a power

1.0

1.0

 

sec.

 

 

 

voltage power failure

input under-voltage can occur

 

 

 

 

 

 

 

 

time

 

without tripping the power

 

 

 

 

 

 

 

 

 

 

failure alarm. Range is 0.3 to

 

 

 

 

 

 

 

 

IPS Time 0001.0s

 

 

 

 

 

 

 

 

25 sec. If under-voltage exists

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

longer than this time, the

 

 

 

 

 

 

 

 

 

 

inverter trips, even if the restart

 

 

 

 

 

 

 

 

 

 

mode is selected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Configuring ParametersDrive

B003

Retry wait time before

Time delay after under-voltage

1.0

1.0

 

sec.

 

 

motor restart

 

condition goes away, before

 

 

 

 

 

 

 

 

 

the inverter runs motor again.

 

 

 

 

 

 

 

IPS Wait 0001.0s

 

 

 

 

 

 

 

 

Range is 0.3 to 100 seconds.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B004

Instantaneous power

Two option codes:

00

00

 

sec.

 

 

 

failure / under-voltage

00... Disable

 

 

 

 

 

 

 

 

trip alarm enable

 

01... Enable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IPS TRIP

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B005

Number of restarts on

Two option codes:

00

00

 

sec.

 

 

 

 

power failure / under-

00... Restart 16 times

 

 

 

 

 

 

 

 

voltage trip events

01... Always restart

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IPS RETRY

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electronic Thermal Overload Alarm Setting

The thermal overload detection protects the inverter and motor from overheating due to an excessive load. It uses a current/inverse time curve to determine the trip point.

First, use B013 to select the torque characteristic that matches your load. This allows the inverter to utilize the best thermal overload characteristic for your application.

Torque

100%

80%

60%

0

Hz

120

The torque developed in a motor is directly proportional to the current in the windings,

which is also proportional to the heat generated (and temperature, over time). Therefore,