3–14

“A” Group: Standard Functions

Configuring

Drive Parameters

 

 

 

 

“A” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

 

Func.

Name /

Description

Mode

–FEF

–FU

 

Units

Edit

 

Code

SRW Display

(EU)

(USA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A005

[AT] selection

Four options, select codes:

00

00

 

Hz

 

 

 

00... Select between [O] and

 

 

 

 

 

 

AT-Slct

O/OI

 

 

 

 

 

 

[OI] at [AT]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01... [O] + [OI] ([AT] input is

 

 

 

 

 

 

 

 

ignored)

 

 

 

 

 

 

 

 

02... Select between [O] and

 

 

 

 

 

 

 

 

keypad potentiometer

 

 

 

 

 

 

 

 

03... Select between [OI] and

 

 

 

 

 

 

 

 

keypad potentiometer

 

 

 

 

 

 

 

 

 

 

 

 

 

A011

Pot./O–L input active

The output frequency corre-

0.0

0.0

 

Hz

 

range start frequency

sponding to the analog input

 

 

 

 

 

 

 

 

range starting point,

 

 

 

 

 

 

O-EXS

0000.0Hz

 

 

 

 

 

 

range is 0.0 to 400.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A012

Pot./O–L input active

The output frequency corre-

0.0

0.0

 

Hz

 

range end frequency

sponding to the analog input

 

 

 

 

 

 

 

 

range ending point,

 

 

 

 

 

 

O-EXE

0000.0Hz

 

 

 

 

 

 

range is 0.0 to 400.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A013

Pot./O–L input active

The starting point (offset) for

0.

0.

 

%

 

range start voltage

the active analog input range,

 

 

 

 

 

 

 

 

range is 0. to 100.

 

 

 

 

 

 

O-EX%S

00000%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A014

Pot./O–L input active

The ending point (offset) for

100.

100.

 

%

 

range end voltage

the active analog input range,

 

 

 

 

 

 

 

 

range is 0. to 100.

 

 

 

 

 

 

O-EX%E

00100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A015

Pot./O–L input start

Two options; select codes:

01

01

 

 

frequency enable

00... Use offset (A011 value)

 

 

 

 

 

 

 

 

01... Use 0 Hz

 

 

 

 

 

 

O-LVL

0Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A016

External frequency

Range n = 1 to 8, where n =

2.

8.

 

Sam-

 

filter time constant

number of samples for avg.

 

 

 

 

ples

 

 

 

 

 

 

 

 

 

 

F-SAMP

00008

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Multi-speed and Jog Frequency Setting

The SJ200 inverter has the capability to store and output up to 16 preset frequencies to the motor (A020 to A035). As in traditional motion terminology, we call this multi-speed profile capability. These preset frequencies are selected by means of digital inputs to the inverter. The inverter applies the current acceleration or deceleration setting to change from the current output frequency to the new one. The first multi-speed setting is duplicated for the second motor settings (the remaining 15 multi-speeds apply only to the first motor).