SJ200 Inverter
Trip History and Inverter Status
We recommend that you first find the cause of the fault before clearing it. When a fault occurs, the inverter stores important performance data at the moment of the fault. To access the data, use the monitor functions (Dxxx) and select D081 for details about the present fault (En). The previous two faults are stored in D082 and D083, with
The following Monitor Menu map shows how to access the error codes. When fault(s) exist, you can review their details by first selecting the proper function: D081 is the most recent, and D083 is the oldest.
Monitor Menu
|
|
|
| 2 | d 0 8 3 |
| 1 |
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
2 |
| d 0 8 1 | 1 |
|
|
|
| 2 |
| d 0 8 2 | 2 | |||||||
|
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Troubleshooting Maintenance and
FUNC.
No error
Error No _ _ _ _
exists?
Yes
Trip
2Conditions
FUNC.
| E 0 9 | Error Code | ||
|
|
|
| |
1 |
|
| 2 |
|
|
| |||
| 1 0.0 | Output frequency | ||
|
|
|
| |
1 |
|
| 2 | at trip point |
|
|
| ||
| 2.5 | Motor current | ||
|
|
|
| |
|
|
|
| at trip point |
12
284.0DC bus voltage
at trip point
1 2
| 1 5 |
| Cumulative inverter | ||
|
| operation time at | |||
1 |
| 2 |
|
| trip point |
| |||||
| 1 8 |
| Cumulative power- | ||
|
|
|
| ||
1 |
|
|
| ON time at trip point | |
|
|
| |||
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
FUNC.