SJ200 Inverter Specifications
Getting Started
General Specifications
The following table applies to all SJ200 inverters.
| Item | General Specifications | ||
|
|
|
|
|
|
|
| ||
Protective housing | *1 | IP20 | ||
|
|
| ||
Control method |
| Sinusoidal Pulse Width Modulation (PWM) control | ||
|
|
| ||
Carrier frequency |
| 2kHz to 14kHz (default setting: 5kHz) | ||
|
| |||
Output frequency range *4 | 0.5 to 400 Hz | |||
|
| |||
Frequency accuracy | Digital command: 0.01% of the maximum frequency | |||
|
|
|
| Analog command: 0.1% of the maximum frequency (25°C ± 10 °C) |
|
| |||
Frequency setting resolution | Digital: 0.1 Hz; Analog: max. frequency/1000 | |||
|
| |||
Volt./Freq. characteristic | V/f optionally variable, V/f control (constant torque, reduced | |||
|
|
|
| torque), intelligent sensorless vector control (iSLV) |
|
|
| ||
Overload capacity |
| 150% of rated current for 1 minute | ||
|
| |||
Acceleration/deceleration time | 0.01 to 3000 seconds, linear and | |||
|
|
|
| accel/decel setting available |
|
|
|
|
|
Input | Freq. |
| Operator panel | Up and Down keys / Value settings |
signal | setting |
|
|
|
| Potentiometer | Analog setting | ||
|
|
| ||
|
|
|
|
|
|
|
| External signal | 0 to 10 VDC (input impedance 10k Ohms), 4 to 20 mA (input |
|
|
| *9 | impedance 250 Ohms), Potentiometer (1k to 2k Ohms, 2W) |
|
|
|
|
|
| FWD/ |
| Operator panel | Run/Stop (Forward/Reverse run change by command) |
| REV |
|
|
|
|
| External signal | Forward run/stop, Reverse run/stop | |
| Run |
| ||
|
|
|
| |
|
|
|
| |
| Intelligent input | FW (forward run command), RV (reverse run command), CF1~CF4 | ||
| terminal |
| ||
|
|
|
| braking), SET (set second motor), 2CH |
|
|
|
| command), FRS (free run stop command), EXT (external trip), USP |
|
|
|
| (startup function), SFT (soft lock), AT (analog current input select |
|
|
|
| signal), RS (reset), TH (thermistor thermal protection), STA (start), |
|
|
|
| STP (stop), F/R (forward/reverse), PID (PID disable), PIDC (PID |
|
|
|
| reset), UP (remote control up function), DWN (remote control down |
|
|
|
| function), UDC (remote control data clearing), OPE (operator |
|
|
|
| control), ADD (ADD frequency enable), |
|
|
|
| mode) |
|
|
| ||
Output | Intelligent output | RUN (run status signal), FA1,2 (frequency arrival signal), OL | ||
signal | terminal |
| (overload advance notice signal), OD (PID error deviation signal), | |
|
|
|
| AL (alarm signal), Dc (analog input disconnect detect), FBV (PID |
|
|
|
| |
|
|
|
| (logic output) |
|
|
| ||
| Frequency monitor | PWM output; Select analog output frequency monitor, analog output | ||
|
|
|
| current monitor or digital output frequency monitor |
|
|
|
| |
Alarm output contact | ON for inverter alarm (1C contacts, both normally open or closed | |||
|
|
|
| avail.) |
|
|
|
|
|