“C” Group: IntelligentTerminal Functions
Network Communication Settings
Configuring | Drive Parameters |
|
|
The following table lists parameters that configure the inverter’s serial communications port. The settings affect how the inverter communicates with a digital operator (such as
|
| “C” Function | Run |
| Defaults |
| |||
|
|
|
|
|
|
|
|
| |
Func. | Name / |
| Description | Mode |
| Units | |||
| Edit |
| |||||||
Code | SRW Display |
| (EU) | (USA) |
| ||||
|
|
|
|
| |||||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
C071 | Communication speed | Three option codes: | ✘ | 06 | 04 |
| baud | ||
| selection |
| 04 | ... 4800 bps |
|
|
|
|
|
|
|
| 05 | ... 9600 bps |
|
|
|
|
|
| COM BAU | 4800 |
|
|
|
|
| ||
| 06 | ... 19200 bps |
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
C072 | Node allocation | Set the address of the inverter | ✘ | 1. | .1 |
| — | ||
|
|
| on the network. Range is 1 to |
|
|
|
|
| |
| COM ADR | 00001 |
|
|
|
|
| ||
| 32. |
|
|
|
|
| |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
C074 | Communication parity | Three option codes: | ✘ | 00 | 00 |
| — | ||
| selection |
| 00 | ... No parity |
|
|
|
|
|
|
|
| 01 | ... Even parity |
|
|
|
|
|
| COM PRTY | NON |
|
|
|
|
| ||
| 02 | ... Odd parity |
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
C075 | Communication stop bit | Range is 1 to 2 | ✘ | 1 | 1 |
| — | ||
| selection |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| COM STP | 1BIT |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
C076 | Communication error | Selects inverter response to | ✘ | 02 | 02 |
| — | ||
| select |
| communications error. |
|
|
|
|
| |
|
|
| Five options: |
|
|
|
|
| |
| COM ESlct | None |
|
|
|
|
| ||
| 00 | ... Trip (error code E60) |
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
|
|
| 01 | ... Decelerate to a stop and |
|
|
|
|
|
|
|
| trip (error code E60) |
|
|
|
|
| |
|
|
| 02 | ... Disable |
|
|
|
|
|
|
|
| 03 | ... Free run stop (coasting) |
|
|
|
|
|
|
|
| 04 | ... Decelerate to a stop |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
C077 | Communication error | Sets the communications | ✘ | 0.00 | 0.00 |
| sec. | ||
|
| watchdog timer period. |
|
|
|
|
| ||
|
|
| Range is 0.00 to 99.99 sec. |
|
|
|
|
| |
| COM ETIM 000.00s |
|
|
|
|
| |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
C078 | Communication wait | Time the inverter waits after | ✘ | 0. | 0. |
| msec. | ||
| time |
| receiving a message before it |
|
|
|
|
| |
|
|
| transmits. |
|
|
|
|
| |
| COM Wait 00000ms |
|
|
|
|
| |||
| Range is 0. to 1000. ms |
|
|
|
|
| |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|