4–6

Control Logic Signal Specifications

Control Logic Signal Specifications

The control logic connectors are located just behind the front housing cover. The relay contacts are just to the left of the logic connectors. Connector labeling is shown below.

Logic inputs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL2

 

AL1

AL0

 

 

 

 

L

6

 

5

4

3

2

 

1

PCS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Relay

 

Analog

 

Analog

 

Logic

 

contacts

 

 

 

 

 

inputs

 

output

outputs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H O OI L AM CM2 12 11

Specifications for the logic connection terminals are in the following table:

 

 

Terminal Name

Description

Ratings

 

 

 

 

 

 

 

 

 

 

 

 

[PCS]

+24V for logic inputs

24VDC, 30 mA max. (do not short to terminal L)

 

 

 

 

 

 

 

[1], [2], [3], [4], [5],

Discrete logic inputs

27VDC max. (use PCS or an external supply refer-

 

 

[6]

 

enced to terminal L)

 

 

 

 

 

 

 

[L] (top row) *1

GND for logic inputs

sum of input [1]—[6] currents (return)

 

 

 

 

 

 

 

[11], [12]

Discrete logic outputs

50mA maximum ON state current,

 

 

 

 

27 VDC maximum OFF state voltage

 

 

 

 

 

 

 

[CM2]

GND for logic outputs

100 mA: sum of 11 and 12 currents (return)

 

 

 

 

 

 

 

[AM]

Analog voltage output

0 to 10VDC, 1mA maximum

Operations Monitoringand

 

 

 

 

 

[L] (bottom row) *2

GND for analog signals

sum of OI, O, H, and AM currents (return)

 

 

 

 

 

 

 

 

 

[OI]

Analog input, current

4 to 19.6 mA range, 20 mA nominal,

 

 

 

 

input impedance 250

 

 

 

 

 

 

 

[O]

Analog input, voltage

0 to 9.8 VDC range, 10VDC nominal,

 

 

 

 

input impedance 10 k

 

 

 

 

 

 

 

[H]

+10V analog reference

10VDC nominal, 10 mA max

 

 

 

 

 

 

 

[AL0]

Relay common contact

250 VAC, 2.5A (R load) max.,

 

 

 

 

250 VAC, 0.2A (I load, P.F.=0.4) max.

 

 

[AL1] *3

Relay contact, normally open

 

 

100 VAC, 10mA min.

 

 

[AL2] *3

Relay contact, normally

30 VDC, 3.0A (R load) max.

 

 

 

closed

30 VDC, 0.7A (I load, P.F.=0.4) max.

 

 

 

 

5 VDC, 100mA min.

 

 

 

 

 

Note 1: The two terminals [L] are electrically connected together inside the inverter.

Note 2: We recommend using the top row [L] logic GND for logic input circuits and the [L] GND on the bottom row of terminals for analog I/O circuits.

Note 3: Default relay N.O./N.C. configuration is reversed. See page 4–35.