Using Intelligent Input Terminals
Software Lock
When the terminal [SFT] is turned ON, the data of all the parameters and functions (except the output frequency, depending on the setting of B031) is locked (prohibited from editing). When the data is locked, the keypad keys cannot edit inverter parameters. To edit parameters again, turn OFF the [SFT] terminal input.
Use parameter B031 to select whether the output frequency is excluded from the lock state or is locked as well.
Option | Terminal | Function Name | Input |
|
|
| Description | ||||||
Code | Symbol | State |
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
15 | SFT | Software Lock | ON | The keypad and remote programming devices | |||||||||
|
|
|
| are prevented from changing parameters | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OFF | The parameters may be edited and stored | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Valid for inputs: | C001, C002, C003, C004, | Example (requires input | |||||||||||
|
| C005, C006 |
| page | |||||||||
Required settings: | B031 (excluded from lock) |
|
|
|
|
| SFT | ||||||
|
|
|
|
|
|
|
|
| |||||
Notes: |
|
|
|
| L | 6 | 5 | 4 | 3 | 2 | 1 | PCS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
•When the [SFT] terminal is turned ON, only the
output frequency can be changed.
• | Software lock can include the output frequency by |
|
|
| setting B031. |
|
|
• | Software lock by the operator is also possible |
|
|
|
| ||
| without the [SFT] terminal being used (B031). | See I/O specs on page | |
|
|
Operations and Monitoring