SJ200 Inverter
Additional Analog Input Settings
Input Range Settings – The parameters in the following table adjust the input characteristics of the analog current input. When using the inputs to command the inverter output frequency, these parameters adjust the starting and ending ranges for the current, as well as the output frequency range. Related characteristic diagrams are located in “Analog Input Settings” on page
|
| “A” Function | Run |
| Defaults |
|
|
| ||
|
|
|
|
|
|
|
|
|
| |
Func. | Name / | Description | Mode |
| Units |
|
| |||
Edit |
|
|
| |||||||
Code | SRW Display | (EU) | (USA) |
|
|
| ||||
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
A101 | The output frequency corre- | ✘ | 0.0 | 0.0 |
| Hz |
|
| ||
| range start frequency | sponding to the current input |
|
|
|
|
|
|
| |
|
|
| range starting point. |
|
|
|
|
|
|
|
| 0000.0Hz |
|
|
|
|
|
|
| ||
| Range is 0.00 to 400.0 Hz |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
A102 | The output frequency corre- | ✘ | 0.0 | 0.0 |
| Hz |
|
| ||
| range end frequency | sponding to the current input |
|
|
|
|
|
|
| |
|
|
| range ending point. |
|
|
|
|
|
|
|
| 0000.0Hz |
|
|
|
|
|
|
| ||
| Range is 0.00 to 400.0 Hz |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
A103 | The starting point for the | ✘ | 0.0 | 0.0 |
| % |
|
| ||
| ||||||||||
| range start current | current input range. |
|
|
|
|
|
| Configuring ParametersDrive | |
|
|
| 01... Use 0Hz |
|
|
|
|
|
| |
| 00000% | Range is 0. to 100.% |
|
|
|
|
|
|
| |
A104 | The ending point for the | ✘ | 100. | 100. |
| % |
|
| ||
| range end current | current input range. |
|
|
|
|
|
|
| |
| 00100% | Range is 0. to 100.% |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
A105 | Two options: | ✘ | 01 | 01 |
| — |
|
| ||
| frequency enable | 00... Use A101 start value |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| 0Hz |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|