SJ200 Inverter
WARNING: In the cases below involving a
1.The unbalance factor of the power supply is 3% or higher.
2.The power supply capacity is at least 10 times greater than the inverter capacity (or the power supply capacity is 500 kVA or more).
3.Abrupt power supply changes are expected, due to conditions such as:
a.Several inverters are interconnected with a short bus.
b.A thyristor converter and an inverter are interconnected with a short bus.
c.An installed phase advance capacitor opens and closes.
Where these conditions exist or when the connected equipment must be highly reliable, you MUST install an
This section will guide you through the following basic steps of installation:
Step | Activity | Page |
|
|
|
|
|
|
1 | Choose a mounting location in compliance with the Warnings and Cautions. | |
See NOTE below. |
| |
|
| |
|
|
|
2 | Check the mounting location for adequate ventilation. | |
|
|
|
3 | Cover the inverter’s ventilation openings to prevent debris from entering. | |
|
|
|
4 | Check the inverter dimensions for footprint and mounting hole locations. | |
|
|
|
5 | Study the Cautions, Warnings, wire and fuse sizes, and terminal torque | |
specifications before wiring the inverter. |
| |
|
| |
|
|
|
6 | Connect wiring for the inverter power input. | |
|
|
|
7 | Wire the inverter output to the motor. | |
|
|
|
8 | Uncover the inverter’s ventilation openings applied in Step 3. | |
|
|
|
9 | Perform the Powerup Test. (This step includes several substeps.) | |
|
|
|
10 | Make observations and check your installation. | |
|
|
|
NOTE: If the installation is in an EU country, study the EMC installation guidelines in Appendix D.
Installation and | Mounting Inverter |
|
|