SJ200 Inverter
“C” Group Intelligent Terminal Functions
Func. | Name | R/W | Description |
| Network Data | ||
|
|
|
| ||||
Code | Reg. |
| Range | Res. | |||
|
|
|
| ||||
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
C146 | Terminal [12] ON delay | R/W | Range is 0.0 to 100.0 sec. | 00F4h |
| 0 to 1000 | 0.1 sec |
|
|
|
|
|
|
|
|
C147 | Terminal [12] OFF | R/W | Range is 0.0 to 100.0 sec. | 00F5h |
| 0 to 1000 | 0.1 sec |
| delay |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
C148 | Output relay ON delay | R/W | Range is 0.0 to 100.0 sec. | 00F6h |
| 0 to 1000 | 0.1 sec |
|
|
|
|
|
|
|
|
C149 | Output relay OFF delay | R/W | Range is 0.0 to 100.0 sec. | 00F7h |
| 0 to 1000 | 0.1 sec |
|
|
|
|
|
|
|
|
Note 1: Assume that the inverter current rating is 10000 (for C041).
The following table lists the holding registers for the “H” Group Motor Constants.
“H” Group Motor Constants
Func. | Name | R/W | Description | Network Data | |||
|
|
| |||||
Code | Reg. | Range | Res. | ||||
|
|
| |||||
|
|
|
| ||||
|
|
|
|
|
|
| |
|
|
|
|
|
|
| |
H003 | Motor capacity | R/W | Thirteen selections: | 00D9h | 0 to 12 | — | |
|
|
| 0..... 0.20 kW |
|
|
| |
H203 | Motor capacity, 2nd | R/W | 00DAh | 0 to 12 | — | ||
1..... 0.37 kW | |||||||
| setting |
|
|
|
| ||
|
| 2..... 0.40 kW |
|
|
| ||
|
|
|
|
|
| ||
|
|
| 3..... 0.55 kW |
|
|
| |
|
|
| 4..... 0.75 kW |
|
|
| |
|
|
| 5..... 1.10 kW |
|
|
| |
|
|
| 6..... 1.50 kW |
|
|
| |
|
|
| 7..... 2.2 kW |
|
|
| |
|
|
| 8..... 3.0 kW |
|
|
| |
|
|
| 9..... 3.7 kW |
|
|
| |
|
|
| 10... 4.0 kW |
|
|
| |
|
|
| 11... 5.5 kW |
|
|
| |
|
|
| 12... 7.5 kW |
|
|
| |
|
|
|
|
|
|
| |
H004 | Motor poles setting | R/W | Four selections: | 00DBh | 2, 4, 6, | 1 pole | |
|
|
| 2 / 4 / 6 / 8 |
| 8 |
| |
|
|
|
|
|
|
| |
H204 | Motor poles setting, 2nd | R/W |
| 00DCh | 2, 4, 6, | 1 pole | |
| motor |
|
|
| 8 |
| |
|
|
|
|
|
|
| |
H006 | Motor stabilization | R/W | Motor constant (factory set), | 00DDh | 0 to 255 | 1 | |
| constant |
| range is 0 to 255 |
|
|
| |
|
|
|
|
|
|
| |
H206 | Motor stabilization | R/W |
| 00DEh | 0 to 255 | 1 | |
| constant, 2nd motor |
|
|
|
|
| |
|
|
|
|
|
|
| |
H007 | Motor voltage select | R/W | Two selections, option codes: | 00DFh | 0, 1 | — | |
|
|
| 00... 200V |
|
|
| |
H207 | Motor voltage select, | R/W | 00E0h | 0, 1 | — | ||
01... 400V | |||||||
| 2nd motor |
|
|
|
| ||
|
|
|
|
|
| ||
|
|
|
|
|
|
|
B Appendix