“B” Group: Fine Tuning Functions
Configuring | Drive Parameters |
|
|
you must set the thermal overload threshold in terms of current (amperes) for parameter B012. The range is 20% to 120% of the rated current for each inverter model. If the current exceeds the level you specify, the inverter will trip and log an event (error E05) in the history table. The inverter turns the motor output OFF when tripped. Separate settings are available for the second motor (if applicable) as shown in the following table.
|
| “B” Function | Run |
| Defaults |
| ||||
|
|
|
|
|
|
|
|
|
| |
Func. | Name / |
|
| Description | Mode |
|
| Units | ||
|
| Edit |
|
| ||||||
Code | SRW Display |
| (EU) |
| (USA) |
| ||||
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| ||||
B012 | Level of electronic | Set a level between 20% and | ✘ | Rated current |
| A | ||||
| thermal setting |
| 120% for the rated inverter |
| for each |
|
| |||
|
|
| current. |
| inverter model |
|
| |||
|
|
|
| |||||||
|
|
|
|
| *1 |
|
| |||
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| ||||
B212 | Level of electronic | Set a level between 20% and | ✘ | Rated current |
| A | ||||
| thermal setting, 2nd | 120% for the rated inverter |
| for each |
|
| ||||
| motor |
| current. |
| inverter model |
|
| |||
|
|
|
|
|
|
| *1 |
|
| |
| 2ETHM LVL 01.60A |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |||
B013 | Electronic thermal | Select from two curves, option | ✘ | 01 |
| 01 |
| — | ||
| characteristic |
| codes: |
|
|
|
|
|
| |
|
|
| 00 | ... Reduced torque 1 |
|
|
|
|
|
|
| CRT |
|
|
|
|
|
| |||
| 01 | ... Constant torque |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| ||
|
|
| 02 | ... Reduced torque 2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
B213 | Electronic thermal | Select from two curves, option | ✘ | 01 |
| 01 |
| — | ||
| characteristic, 2nd | codes: |
|
|
|
|
|
| ||
| motor |
| 00 | ... Reduced torque 1 |
|
|
|
|
|
|
|
|
| 01 | ... Constant torque |
|
|
|
|
|
|
| 2ETHM CHAR | CRT |
|
|
|
|
|
| ||
| 02 | ... Reduced torque 2 |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
Note 1: For inverter models 005NFEF, 011NFEF, and 030HFEF, the thermal value is less than the rated amperes (is the same as models 004NFEF, 007NFEF, and 040HFEF respectively). Therefore, be sure to set the electronic thermal overload according to the actual motor driven by the particular inverter.
WARNING: When parameter B012, level of electronic thermal setting, is set to motor FLA rating (Full Load Ampere nameplate rating), the inverter provides solid state motor overload protection at 115% of motor FLA or equivalent. If parameter B012 exceeds the motor FLA rating, the motor may overheat and be damaged. Parameter B012, level of electronic thermal setting, is a variable parameter.