SJ200 Inverter
Troubleshooting Tips
The table below lists typical symptoms and the corresponding solution(s).
Symptom/condition | Probable Cause | Solution | |
|
|
|
|
|
|
|
|
|
| • Is the frequency command source | • Make sure the parameter |
|
| A001 parameter setting correct? | setting A001 is correct. |
|
| • Is the Run command source A002 | • Make sure the parameter |
|
| parameter setting correct? | setting A002 is correct. |
|
|
|
|
|
| • Is power being supplied to termi- | • Check terminals [L1], [L2], |
|
| nals [L1], [L2], and [L3/N]? If so, | and [L3/N], then [U/T1], |
|
| the POWER lamp should be ON. | [V/T2], and [W/T3]. |
|
|
| • Turn ON the power supply |
|
|
| or check fuses. |
|
|
|
|
|
| • Is there an error code E X X | • Press the Func. key and |
| The inverter | displayed? | determine the error type. |
|
| Eliminate the error cause, | |
| outputs [U], [V], |
| then clear the error (Reset). |
| [W] are not |
|
|
| • Are the signals to the intelligent | • Verify the terminal functions | |
| supplying | ||
| input terminals correct? | for C001 – C006 are correct. | |
| voltage. | ||
| • Is the Run Command active? | • Turn ON Run Command | |
The motor |
| ||
| • Is the [FW] terminal (or [RV]) | enable. | |
will not run. |
| ||
| connected to [PCS] (via switch, | • Supply 24V to [FW] or [RV] | |
|
| ||
|
| etc.) | terminal, if configured. |
|
|
|
|
|
| • Has the frequency setting for F001 | • Set the parameter for F001 |
|
| been set greater than zero? | to a safe, |
|
| • Are the control circuit terminals | • If the potentiometer is the |
|
| [H], [O], and [L] connected to the | frequency setting source, |
|
| potentiometer? | verify voltage at [O] > 0V. |
|
|
|
|
|
| • Is the RS (reset) function or FRS | • Turn OFF the command(s). |
|
|
| |
|
|
|
|
| Inverter outputs | • Is the motor load too heavy? | • Reduce load, and test the |
| [U], [V], [W] |
| motor independently. |
| are supplying |
|
|
| voltage. |
|
|
|
|
|
|
| The optional | • Are the operational settings | • Check the operator type |
| remote operator | between the remote operator and | setting. |
| is used (SRW). | the inverter unit correct? |
|
|
|
|
|
|
| • Are the connections of output | • Make connections according |
|
| terminals [U/T1], [V/T2], and | to the phase sequence of the |
|
| [W/T3] correct? | motor. In general: |
|
| • Is the phase sequence of the motor | FWD = |
The direction of the motor is | forward or reverse with respect to | ||
| |||
[U/T1], [V/T2], and [W/T3]? |
| ||
reversed. |
| ||
|
| ||
|
| • Are the control terminals [FW] and | • Use terminal [FW] for |
|
| [RV] wired correctly? | forward, and [RV] for |
|
| • Is parameter F004 properly set? | reverse. |
|
|
| • Set motor direction in F004. |
|
|
|
|