“B” Group: Fine Tuning Functions
Software Lock Mode
Configuring | Drive Parameters |
|
|
The software lock function keeps personnel from accidentally changing parameters in the inverter memory. Use B031 to select from various protection levels.
The table below lists all combinations of B031 option codes and |
|
|
|
| Run |
| |
the ON/OFF state of the [SFT] input. Each Check ✔ or Ex ✘ |
|
| |
| Mode |
| |
indicates whether the corresponding parameter(s) can be edited. |
|
| |
| Edit |
| |
The Standard Parameters column below shows access is permit- |
|
| |
|
|
| |
| ✘ |
| |
ted for some lock modes. These refer to the parameter tables |
|
| |
|
|
| |
| ✔ |
| |
throughout this chapter, each of which includes a column titled |
|
| |
Run Mode Edit as shown to the right. The marks (Check ✔ or |
|
|
|
|
|
|
Ex ✘) under the “Run Mode Edit” column title indicate whether access applies to each parameter as defined in the table below. In some lock modes, you can edit only F001 and the
B031 | [SFT] | Standard Parameters | F001 and |
| B031 | ||
| |||||||
Lock | Intelligent |
|
|
|
|
| |
|
|
|
|
|
| ||
Mode | Input | Stop | Run | Stop & Run | Stop |
| Run |
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
00 | OFF | ✔ | Run mode | ✔ | ✔ |
| ✘ |
|
|
| edit access |
|
|
|
|
|
|
|
|
|
|
|
|
| ON | ✘ | ✘ | ✘ | ✔ |
| ✘ |
|
|
|
|
|
|
|
|
01 | OFF | ✔ | Run mode | ✔ | ✔ |
| ✘ |
|
|
| edit access |
|
|
|
|
|
|
|
|
|
|
|
|
| ON | ✘ | ✘ | ✔ | ✔ |
| ✘ |
|
|
|
|
|
|
|
|
02 | (ignored) | ✘ | ✘ | ✘ | ✔ |
| ✘ |
|
|
|
|
|
|
|
|
03 | (ignored) | ✘ | ✘ | ✔ | ✔ |
| ✘ |
|
|
|
|
|
|
|
|
NOTE: Since the software lock function B031 is always accessible, this feature is not the same as password protection used in other industrial control devices.