SJ200 Inverter
Thermistor Thermal Protection
Motors that are equipped with a thermistor can be protected from overheating. Input terminal [6] has the unique ability to sense a thermistor resistance. When the resistance value of the thermistor connected to terminal [TH] (6) and [L] is more than 3 k Ω ±10%, the inverter enters the Trip Mode, turns OFF the output to the motor, and indicates the trip status E35. Use this function to protect the motor from overheating
Option | Terminal | Function Name | Input |
|
|
|
|
|
|
|
| Description | |||||||
Code | Symbol | State |
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
19 | TH | Thermistor Thermal | Sensor | When a thermistor is connected to terminals [6] | |||||||||||||||
|
| Protection |
| and [L], the inverter checks for | |||||||||||||||
|
|
|
| and will cause trip (E35) and turn OFF the | |||||||||||||||
|
|
|
| output to the motor | |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Open | An open circuit in the thermistor causes a trip, | |||||||||||||||
|
|
|
| and the inverter turns OFF the output | |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Valid for inputs: | C006 only |
| Example (requires input configuration— | ||||||||||||||||
|
|
|
| see page | |||||||||||||||
Required settings: | C085 |
| |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| TH | ||||||||||
Notes: |
|
|
|
|
|
|
|
| |||||||||||
• Be sure the thermistor is connected to terminals [6] |
| L | 6 | 5 | 4 | 3 | 2 | 1 | PCS |
| |||||||||
and [L]. If the resistance is above the threshold the |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
inverter will trip. When the motor cools down |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
enough, the thermistor resistance will change |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
enough to permit you to clear the error. Press the |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
STOP/Reset key to clear the error. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| thermistor | |||||||||||||||||
|
|
|
|
| |||||||||||||||
|
|
|
|
|
| MOTOR | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|