SJ200 Inverter
PID Loop Configuration
The inverter’s PID loop algorithm is configurable for various applications.
PID Output Limit - The PID loop controller has a
•When the difference (Setpoint – loop output) is smaller than or equal to the A078 limit value, the loop controller operates in its normal linear range.
•When the difference (Setpoint – loop output) is larger than the A078 limit value, the loop controller changes the output frequency as needed so that the difference does not exceed the limit.
The diagram below shows PID setpoint changes and the related output frequency behavior when a limit value in A078 exists.
% |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Output limit |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Limit imposed |
| ||||||||||||
|
|
|
|
|
|
|
| |||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| on output |
| ||||||||
|
|
|
| A078 | Limit value |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PID Setpoint
Output frequency A078
Limit value
Output limit |
|
|
|
|
|
|
| Limit imposed |
|
|
|
| |||||
|
|
|
|
|
|
|
| on output |
t
Error Inversion - In typical heating loops or ventilation loops, an increase in energy into the process results in an increasing PV. In this case, the Loop Error = (SP – PV). For cooling loops, an increase in energy into the process results in a decreasing PV. In this case, the Loop Error =
A077 = 00 |
|
|
|
|
|
| A077 = 01 |
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SP + ∑ |
| Error |
| Freq. |
| SP – ∑ |
| Error |
| Freq. | ||||||||||
| PID |
| PID | |||||||||||||||||
|
|
|
|
|
| Calculation |
|
|
|
|
|
|
|
|
|
| Calculation |
|
|
|
PV |
| – |
|
|
|
|
| PV |
| + |
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
| PV from process with |
|
|
| PV from process with | ||||||||||||||
|
|
|
|
|
|
|
| |||||||||||||
|
|
|
| positive correlation |
|
|
|
| negative correlation | |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|