SJ200 Inverter
breakpoint of the boost (point A on the graph) by using parameters A042 and A043. The manual boost is calculated as an addition to the standard V/f curve.
NOTE: Manual torque boost is not operational when intelligent sensorless vector control is in use.
Be aware that running the motor at a low speed for a long time can cause motor overheating. This is particularly true when manual torque boost is ON, or if the motor relies on a
NOTE: Manual torque boost applies only to constant torque (A044=00) and variable torque (A044=01) V/f control.
Voltage Gain – Using parameter A045 you can modify the voltage gain of the inverter (see graph at right). This is specified as a percentage of the full scale output voltage. The gain can be set from 20% to 100%. It should be adjusted in accordance with the motor specifi- cations.
V 100%
20%
Voltage Gain
A045
0 | Hz |
|
Intelligent Sensorless Vector Control (iSLV) – This advanced torque control algorithm improves torque performance at very low
NOTE: You must disable intelligent sensorless vector operation when two or more motors are connected (parallel operation) to the inverter.
NOTE: If the inverter experiences
The following table shows the methods of torque control selection.
| “A” Function | Run |
| Defaults |
| ||
|
|
|
|
|
|
| |
Func. | Name / | Description | Mode |
| Units | ||
Edit |
| ||||||
Code | SRW Display | (EU) | (USA) |
| |||
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
A042 | Manual torque boost | Can boost starting torque | ✔ | 5.0 | 5.0 |
| % |
| value | between 0 and 20% above |
|
|
|
|
|
|
| normal V/f curve, |
|
|
|
|
|
|
|
|
|
|
| ||
| range is 0.0 to 20.0% |
|
|
|
|
| |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
Parameters Drive | Configuring |