SJ200 Inverter
The inverter has other control sources that can temporarily override the parameter A001 setting, forcing a different output frequency source. The following table lists all frequency source setting methods and their relative priority (“1” is the highest priority).
Priority | A001 Frequency Source Setting Method | Refer to page... |
|
|
|
|
|
|
1 | [CF1] to [CF4] | |
|
|
|
2 | [OPE] Operator Control intelligent input | |
|
|
|
3 | ||
|
|
|
4 | [AT] terminal | |
|
|
|
5 | TM/PRG DIP Switch - (if switch is in “TM” position) | |
|
|
|
6 | A001 Frequency source setting | |
|
|
|
The inverter also has other control sources that can temporarily override the parameter A002 setting, forcing a different Run command source. The following table lists all Run command setting methods and their relative priority (“1” is the highest priority).
Priority | A002 Run Command Setting Method | Refer to page... |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 | [OPE] Operator Control intelligent input |
| ParametersDrive |
| |
|
|
|
|
| |
2 |
| Configuring | |||
|
|
|
| ||
3 | TM/PRG DIP Switch - (if switch is in “TM” position) |
| |||
|
|
| |||
|
|
|
|
|
|
4 | A002 Run command source setting |
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|