SJ200 Inverter
Analog Output Operation
In inverter applications it is useful to monitor the inverter operation from a remote location or from the front panel of an inverter enclosure. In some cases, this requires only a
H O OI L AM CM2 12 11
|
|
|
| – |
|
| + |
| Analog |
|
| A GND |
|
|
|
| |||||
|
|
| Voltage Output | |||||||
|
|
|
|
|
|
| ||||
10VDC |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| ||
full scale, |
|
|
|
|
|
|
|
|
| |
1mA max |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
See I/O specs on page
The inverter provides an analog voltage output on terminal [AM] with terminal [L] as analog GND reference. The [AM] can output inverter frequency or current output value. Note that the voltage range is 0 to +10V
Func. | Code | Description | Range | |
|
|
|
| |
|
|
|
| |
C028 | 00 | Output frequency | 0 – Max. frequency (Hz) | |
|
|
| ||
01 | Output current | 0 – 200% | ||
| ||||
|
|
|
|
The [AM] signal offset and gain are adjustable, as indicated below.
Func. | Description | Range | Default |
|
|
|
|
|
|
|
|
B080 | [AM] analog signal gain | 0 to 255 | 100 |
|
|
|
|
C086 | [AM] terminal offset tuning | 0 – 10V | 0.0 |
|
|
|
|
The graph to the right shows the effect of the gain setting. To calibrate the [AM] output for your application, follow the steps below:
1.Verify that the inverter is in Stop Mode.
2.Use C086 to adjust the offset voltage. The factory default (0V) is the correct value for most cases. Otherwise, you can have a positive voltage at zero speed or current.
3.Run the motor at the full scale speed.
a.If [AM] represents output frequency, use B080 to set the voltage for full scale output (up to 10V).
[AM]
B080=200% 10V
B080=100%
5V B080=50%
0
1/2 full | Full | Hz |
scale | scale | or |
| output | A |
Operations Monitoring and
b.If [AM] represents motor current, use B080 to set the voltage for full scale output. Remember to leave room at the upper end of the range for increased current when the motor is under heavier loads.