“A” Group: Standard Functions
PID Control
Configuring | Drive Parameters |
|
|
When enabled, the
•A scale factor in A075 lets you multiply the PV by a factor, converting it into engineering units for the process.
•Proportional, integral, and derivative gains are all adjustable.
•See “PID Loop Operation” on page
|
| “A” Function | Run |
| Defaults |
| |||
|
|
|
|
|
|
|
|
| |
Func. | Name / |
| Description | Mode |
| Units | |||
| Edit |
| |||||||
Code | SRW Display |
| (EU) | (USA) |
| ||||
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
A071 | PID Enable |
| Enables PID function, | ✘ | 00 | 00 |
| — | |
|
|
| two option codes: |
|
|
|
|
| |
| PID Mode | OFF |
|
|
|
|
| ||
| 00 | ... PID Disable |
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
|
|
| 01 | ... PID Enable |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
A072 | PID proportional gain | Proportional gain has a range | ✔ | 1.0 | 1.0 |
| — | ||
|
|
| of | 0.2 to 5.0 |
|
|
|
|
|
| PID P | 0001.0 |
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
A073 | PID integral time | Integral time constant has a | ✔ | 1.0 | 1.0 |
| sec. | ||
| constant |
| range of 0.0 to 150 seconds |
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| PID I | 0001.0s |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
A074 | PID derivative time | Derivative time constant has a | ✔ | 0.0 | 0.0 |
| sec. | ||
| constant |
| range of 0.0 to 100 seconds |
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| PID D | 000.00s |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
A075 | PV scale conversion | Process Variable (PV) scale | ✘ | 1.00 | 1.00 |
| — | ||
|
|
| factor (multiplier), range of |
|
|
|
|
| |
| PID Cnv | 001.00% |
|
|
|
|
| ||
| 0.01 to 99.99 |
|
|
|
|
| |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
A076 | PV source setting | Selects source of Process | ✘ | 00 | 00 |
| — | ||
|
|
| Variable (PV), option codes: |
|
|
|
|
| |
| PID INP | OI |
|
|
|
|
| ||
| 00 | ... [OI] terminal (current in) |
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
|
|
| 01 | ... [O] terminal (voltage in) |
|
|
|
|
|
|
|
| 02 | ... ModBus network |
|
|
|
|
|
|
|
| 03 | ... Calculate function output |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
A077 | Reverse PID action | Two option codes: | ✘ | 00 | 00 |
| — | ||
|
|
| 00 | ... PID input = SP – PV |
|
|
|
|
|
| PID MINUS | OFF |
|
|
|
|
| ||
| 01 | ... PID input = |
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
A078 | PID output limit | Sets the limit of PID output as | ✘ | 0.0 | 0.0 |
| % | ||
|
|
| percent of full scale, |
|
|
|
|
| |
| PID Vari 0000.0% |
|
|
|
|
| |||
| range is 0.0 to 100.0% |
|
|
|
|
| |||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
NOTE: The setting A073 for the integrator is the integrator’s time constant Ti, not the gain. The integrator gain Ki = 1/Ti. When you set A073 = 0, the integrator is disabled.