SJ200 Inverter
ModBus Holding Registers
The following tables list the holding registers for the inverter interface to the network. The table legend is given below.
•Function Code - The inverter’s reference code for the parameter or function (same as inverter keypad display)
•Name - The standard functional name of the parameter or function for the inverter
•R/W - The
•Description - How the parameter or setting works (same as Chapter 3 description).
•Reg. - The network register address to the value (some values have a
•Range - The numerical range for the network value that is sent and/or received
TIP: The network values are binary integers. Since these values cannot have an embedded decimal point, for many parameters it represents the actual value (in engineering units) multiplied by a factor of 10 or 100. Network communications must use the listed range for network data. The inverter automatically divides received values by the appropriate factor in order to establish the decimal point for internal use. Likewise, the network host computer must apply the same factor when it needs to work in engineering units. However, when sending data to the inverter, the network host computer must scale values to the integer range listed for network communications.
•Resolution - This is the quantity represented by the LSB of the network value, in engineering units. When the network data range is greater than the inverter’s internal data range, this
List of Holding Registers
Func. | Name | R/W | Description |
| Network Data | ||
|
|
|
| ||||
Code | Reg. |
| Range | Res. | |||
|
|
|
| ||||
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
— | Output frequency |
| Inverter output frequency (set | 001h |
| 0 to | 0.1 Hz |
| command |
| A001=03 to enable this |
|
| 4000 |
|
|
|
| network register), |
|
|
|
|
|
|
| range is 0.0 to 400.0 Hz |
|
|
|
|
|
|
|
|
|
|
|
|
— | Inverter status | R/W | 00... Initial status | 002h |
| 0 to 9 | — |
|
|
| 01... (Reserved) |
|
|
|
|
|
|
| 02... Stop Mode |
|
|
|
|
|
|
| 03... Run Mode |
|
|
|
|
|
|
| 04... |
|
|
|
|
|
|
| 05... Jogging |
|
|
|
|
|
|
| 06... DC braking |
|
|
|
|
|
|
| 07... Retry |
|
|
|
|
|
|
| 08... Trip alarm |
|
|
|
|
|
|
| 09... |
|
|
|
|
|
|
|
|
|
|
|
|
— | Process Variable (PV) |
| PID loop PV value from the | 003h |
| 0 to | 0.1% |
|
|
| network (set A076=02 to |
|
| 1000 |
|
|
|
| enable this setting), range is |
|
|
|
|
|
|
| 0.0 to 100.0% |
|
|
|
|
|
|
|
|
|
|
|
|
B Appendix