Using Intelligent Input Terminals
External Signal for DC Braking
When the terminal [DB] is turned ON, the DC braking feature is enabled. Set the following parameters when the external DC braking terminal [DB] is to be used:
[FW, RV]
Scenario 1
1
0
•A053 – DC braking delay time setting. The range is 0.1 to 5.0 seconds.
•A054 – DC braking force setting. The range is 0 to 100%.
The scenarios to the right help show how DC braking works in various situations.
1. | Scenario 1 – The [FW] or [RV] terminal is |
| ON. When [DB] is ON, DC braking is |
| applied. When [DB] is OFF again, the |
| output frequency ramps to the prior level. |
2. | Scenario 2 – The Run command is applied |
| from the operator keypad. When the [DB] |
| terminal is ON, DC braking is applied. |
| When the [DB] terminal is OFF again, the |
| inverter output remains OFF. |
3. | Scenario 3 – The Run command is applied |
| from the operator keypad. When the [DB] |
| terminal is ON, DC braking is applied |
1
[DB] 0
Output frequency
t
Scenario 2
Run command 1 from operator 0
1
[DB] 0
Output frequency
t
Scenario 3
Run command 1 (from operator) 0 1
[DB] 0
after the delay time set by A053 expires. |
The motor is in a |
Output
delay A053
condition. When the [DB] terminal is OFF |
again, the inverter output remains OFF. |
frequency
t
Operations and Monitoring
Option | Terminal | Function Name | Input |
|
|
| Description | |||||||
Code | Symbol | State |
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
07 | DB | External DC Braking | ON | applies DC injection braking during deceleration | ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OFF | does not apply DC injection braking during | ||||||||||
|
|
|
| deceleration | ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Valid for inputs: | C001, C002, C003, C004, | Example (requires input | ||||||||||||
C005, C006 |
| |||||||||||||
|
|
| page | |||||||||||
|
|
|
| |||||||||||
Required settings: | A053, A054 |
|
|
|
|
|
| DB |
| |||||
|
|
|
|
|
|
|
|
| ||||||
Notes: |
|
|
|
| L | 6 | 5 | 4 | 3 | 2 | 1 | PCS |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
•Do not use the [DB] input continuously or for a
long time when the DC braking force setting A054 is high (depends on the motor application).
•Do not use the [DB] feature for continuous or high
duty cycle as a holding brake. The [DB] input is |
|
designed to improve stopping performance. Use a | See I/O specs on page |
mechanical brake for holding a stop position. |