SJ200 Inverter
Action | Display | Func./Parameter |
|
|
|
(Starting point) |
|
| A 0 0 3 | Base frequency setting | ||
|
|
| ||||
|
|
|
|
|
|
|
Press the | 1 | key and hold | A 0 8 2 | AVR voltage select | ||
| ||||||
|
|
|
|
|
| |
|
|
|
|
|
|
|
Press the FUNC. key. |
| 2 3 0 | Default values for AVR voltage: | |||
| 200V class = 230VAC | |||||
|
|
|
|
| or | 400V class = 400VAC |
|
|
|
|
| 4 0 0 | 400V class = 460VAC |
|
|
|
|
|
| |
|
|
|
|
|
|
|
Press the | 1 | or | 2 | key as needed. | 2 1 5 | Set to your motor specs (your |
display may be different) | ||||||
|
|
|
|
| ||
|
|
|
|
|
|
|
Press the STR | key. |
| A 0 8 2 | Stores parameter, returns to “A” | ||
| Group list |
Set the Motor Current - The inverter has thermal overload protection that is designed to protect the inverter and motor from overheating due to an excessive load. The inverter’s uses the motor’s current rating to calculate the
Read the motor’s current rating on its manufacturer’s nameplate. Then follow the steps below to configure the inverter’s thermal overload protection setting.
Action | Display | Func./Parameter |
|
|
|
(Starting point) |
|
| A 0 8 2 | Base frequency setting | ||
|
|
| ||||
|
|
|
|
|
|
|
Press the FUNC. key. |
|
| A – – – | “A” Group selected | ||
|
|
| ||||
|
|
|
|
|
|
|
Press the | 1 | key. |
|
| b – – – | “B” Group selected |
|
|
| ||||
|
|
|
|
|
| |
|
|
|
|
|
|
|
Press the FUNC. key. |
|
| b 0 0 1 | First “B” Group parameter | ||
|
| selected | ||||
|
|
|
|
|
|
|
Press the | 1 | key and hold | b 0 1 2 | Level of electronic thermal setting | ||
| ||||||
|
|
|
|
|
| |
|
|
|
|
|
|
|
Press the FUNC. key. |
| 1.60 | Default value will be 100% of | |||
| inverter rated current. | |||||
|
|
|
|
|
|
|
Press the | 1 | or | 2 | key as needed. | 1.80 | Set to your motor specs (your |
display may be different) | ||||||
|
|
|
|
| ||
|
|
|
|
|
|
|
Press the STR | key. |
| B 0 1 2 | Stores parameter, returns to “B” | ||
| Group list |
Installation and | Mounting Inverter |
|
|