“A” Group: Standard Functions
Run Command Source Setting - For parameter A002, the following table provides a further description of each option, and a reference to other page(s) for more information
Code | Run Command Source | Refer to page(s)... |
|
|
|
|
|
|
01 | Control terminal - The [FW] or [RV] input terminals control | |
| Run/Stop operation |
|
|
|
|
02 | Keypad Run key - The Run and Stop keys provide control | |
|
|
|
03 | ModBus network input - The network has a dedicated coil | |
| for Run/ Stop command and a coil for FW/RV |
|
|
|
|
A001/A002 Override Sources - The inverter allows some sources to override the settings for output frequency and the Run command in A001 and A002. This provides flexibility for applications that occasionally need to use a different source, leaving the standard settings in A001/A002. In particular, note the TM/PRG (Terminal/Program) DIP switch behind the front panel cover shown below. It is the switch to the right.
Configuring | Drive Parameters |
|
|
SR 485 TM
SK
OPEPRG
The TM/PRG switch setting forces terminal operation, according to the table below:
TM/PRG | Item | Source | |
Switch Position | |||
|
| ||
|
|
| |
|
|
| |
PRG (Program) | Output frequency source | Specified by A001 setting | |
|
| ||
Run command source | Specified by A002 setting | ||
| |||
|
|
| |
TM (Terminal) | Output frequency source | [O] or [OI] analog input terminal | |
|
| ||
Run command source | [FW] and/or [RV] input terminals | ||
| |||
|
|
|
When A001 = 01 and A002 = 01, the inverter control source is the terminals, regardless of the TM/PRG switch position. When A001 and A002 setting is not 01, then the TM/PRG switch can force terminal input control.